Installation manual
9EcoBreeze System Operation and Maintenance
Electrical inspection checklist
The electrical inspection verifies that all electrical connections are secure and correct and that
the equipment is properly grounded.
CAUTION
ELECTRICAL HAZARD
• All electrical wiring must comply with local and national codes and regulations.
• The equipment must be grounded (do not use a water-pipe ground).
Failure to follow these instructions can result in injury or equipment damage.
Ensure that the:
Incoming voltages match the phase and voltage listing on the nameplate.
Electrical wiring complies with local and national codes and regulations.
Equipment is properly grounded.
Electrical connections are tight, including contactors, terminal blocks, controllers, switches,
relays, auxiliary devices, and field connections.
Check wiring to the pump motors and water treatment system.
Main power branch is sized appropriately for the unit.
Main electric supply is properly wired to power source and frame.
Remote interface panel is mounted and wired to the frame.
Field wiring has been installed for (optional) Modbus, alarm contact and remote shutdown if
applicable.