Network Management Card & Modbus/ Jbus (66123) Installation manual
- 3402230800/AC
The Network Management Card & Modbus/Jbus (66123) is recommended for central UPSs protecting entire networks or for UPS units backing up critical loads.
. OVERVIEW Jbus/modbus port MAC address ETHERNET 10/100BT port 000623001C07 Service port (Settings/Sensor) Orange LED: RS232 activity Settin gs/Sen 100M sor 10M UPS data RS232 6612 3 Green LED: communication with the UPS Catalogue number Orange LED: 10/100M Green LED: connection + activity INDICATIONS ETHERNET port LED Colour ACT Green 100M Orange Status ◗ OFF ◗ ON ◗ Flashing ◗ OFF ◗ ON Description ◗ Card not connected to network ◗ Card connected to network, but no activity ◗ Port is se
The Network Management Card & Modbus/Jbus (66123) can be hot-plugged in MGETM GalaxyTM 7000 equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart the UPS. ◗ Note the MAC address of the card before inserting it. UPS Settings/ Sensor 100M 10M UPS data RS232 66103 ETHERNET ◗ Insert and secure the card with the screws. ◗ Connect the ETHERNET cable. ◗ Check the ETHERNET port indications. ◗ Wait until the UPS Data LED flashes regularly (approx.
Your network is equipped with a BOOTP/DHCP server (default) The card is configured by default with this service enabled. No manual configuration is required.The IP parameters are automatically collected by the card. From the main configuration menu: (see above) ◗ Press the 2 key (Network configuration). ◗ Press the 1 key(Read Network settings). The settings supplied by the server are displayed: Network configuration : MAC address : 00:06:23:00:1C:07 Mode : DHCP IP address : 172.17.23.18 Subnet mask : 255.
ACCESS TO SUPERVISION To check whether the Network Management Card & Modbus/Jbus (66123) is operational after installation and configuration, proceed as follows. ◗ Run a browser ◗ Enter in the address bar: http://IP address/ (e.g. http://172.16.1.82/) ◗ The home page is displayed ◗ Set the time by clicking the Time command. ◗ Continue configuration via the sections in the Settings menu.
SENSOR CONNECTION (option) ETHERNET The Environment sensor is a Network Management Card & Modbus/Jbus option. The sensor remotely monitors the UPS environment by regularly measuring the temperature and humidity, and checking the states of two external contacts. It can also send alarms (e-mail, SNMP trap) tripped by pre-set thresholds. Connection is made via the Service port (Settings/Sensor) on the Network Management Card & Modbus/ Jbus. The sensor is detected automatically.
JBUS/MODBUS RS232 link configuration and connection SA1 SA2 Pin Function 4 SG 3 2 1 Txd SA2 Received data (input) Not connected Transmitted data (output) Not connected Signal ground 1 8 OFF ON 5 1 2 3 4 5 Rxd RS485 link configuration and connection For proper operation, the polarity of EIA RS485 2-wire and 4-wire lines must be set at only one point and the lines terminated at the end. Polarity Normally, the master of the network sets the polarity of the line.
2 wires connection SA1 SA2 SA2 3 2 1 L- L+ 8 8 5V OFF ON 4 1 OFF ON 5 SA1 1 3V3 3V3 Rp polarity L- Ra L- connection if end of the line L- 1 3 L- 3 termination Ra connection if end of the line 7 L+ 1 3 Ra termination SA1-3 SA1-3 L+ L+ 2 polarity L+ 4 2 4 Rp 0V 0V transmit/receive data 0V transmit/receive data Card of an intermediate cabinet Master unit Card settings of an intermediate cabinet ON OFF 8 78 67 56 45 34 23 12 1 SA1 SA1 SA1 Link without polarit
4 wires connection SA2 SA1 SA2 3 T+ T- Rp 2 1 8 R + R- master transmitt 5V 8 OFF ON 4 1 OFF ON 5 SA1 1 slave receiver polarity T- R- slave receiver R- Rtermination 1 Ra 1 Ra termination T+ polarity R+ 2 R+ R+ 2 Rp 0V Rp Ra transmit data receive data receive data 5V slave receiver R- slave transmitt T- connection if end of the line T- T- 3 slave transmitt 3 connection if end of the line R+ T+ 4 T+ T+ 4 Rp 0V receive data Master unit transmit data Card
Configuration of the JBUS/MODBUS communication parameters ETHERNET Through settings port ETHE RNET Setting s/Sens or 100M 100M On = Blink Link = Act 10M 10M UPS UPS data data RS232 RS23 2 66103 661 02 100M 10M UPS data RS232 66103 UPS Connect the RS232 link to a terminal (Microsoft Hyper terminal) ◗ Use the cord supplied with the card ◗ Connect the card to a computer ◗ Use a terminal emulator such as HyperTerminalTM with these settings Bits per second Data bits Stop bits 9600 8 1 "Echo type
◗ Press the 2 key (Modifiy Jbus settings) ◗ Press «Return» key to modify the Jbus settings Setting Jbus configutration Set Slave number : 0x1* Set the Baud Rate [1:38400,2: 19200, 3:9600, 4: 4800, 5: 2400, 6: 1200] :3 Set data format[1: 8 bits, 2: 7 bits] :1 Set stop bit[1: 1 bits, 2: 2 bits] :1 Set parity [1: None, 2: Even, 3: Odd] :1 Wait during the new setting is saved ... TLS/Slave JBUS initialized The Jbus configuration is now updated. * Hex format. ◗ Press the 0 key (Exit). ◗ Press the 0 key (Exit).
◗ Set the parameters. ◗ Select the «Save» button to save the new parameters.
TECHNICAL CHARACTERISTICS Physical characteristics Dimensions (W x D x H) 132 x 66 x 42 mm Weight 70 g RoHS 100% compatible Storage Storage temperature range -10°C to 70°C Ambient conditions Operating temperature range 0°C to 40°C Relative humidity 90% RH max. without condensation Card performance Supply voltage 5V ±5% Supply current (all LEDs ON and Environment Sensor connected) 300 mA max. Functions Web supervision 5 browsers max. (http), 3 browsers max.
ELECTROMAGNETIC COMPATIBILITY When correctly installed and used in accordance with manufacturer instructions, the card complies with the following standards: ◗ ITE (Information Technology Equipment) safety: IEC/EN 60950-1 2005 ◗ EMC: EN 61000-6-2 (2005), EN 61000-6-3 (2006), IEC/EN 62040-2 (2005) In compliance with European directives: ◗ Low voltage: 2006/95/EEC. ◗ EMC: 2004/108/EEC.