Specifications

Installation Procedures: Route and Attach Overhead Wiring
150 kW InfraStruXure Power Distribution Unit 27
For dual-feed devices within a redundant system: Attach a power cable from each PDU to
two different rack PDUs in the NetShelter VX enclosure.
For single-feed devices within a redundant system with an automatic transfer switch:
Connect a power cable to the automatic transfer switch (A and B feeds) and connect the
automatic transfer switch power cord to a rack PDU in the NetShelter VX enclosure.
For dual-feed devices in a redundant system with an automatic transfer switch: Connect a
power cable from each PDU to the automatic transfer switch’s A and B feeds, and another
power cable from one PDU to a rack PDU, and the automatic transfer switch power cord to a
second rack PDU in the NetShelter VX enclosure.
Note
Lay the cables neatly in the shielding trough to minimize cable build-up.