Specifications

Installation Procedures: Connect User Input Contacts and Relay Outputs to the User Connection Plate
22 150 kW InfraStruXure Power Distribution Unit
To connect and monitor your contacts
1. Choose one or more contact numbers on the User/EPO contacts port on the user connection
plate. The user connection plate connects to the PDU monitoring unit.
2. From the PDU display interface:
a. Press
ESC or ENTER to go to the top-level menu screen.
b. Select Contacts from the top-level menu screen and press
ENTER.
c. Select Contact Inputs (or Relay Outputs) and press
ENTER to display the contact inputs (or
relay outputs) screen.
d.
d. Select Contact In and press ENTER to select the number of the contact you are connecting.
The continue arrow will appear next to the contact number. Press the Up or Down arrow to
go to the appropriate contact number and press
ENTER.
e. Press the Down arrow to enter a unique Name for the contact and to configure the Normal
state of the contact (Open or Closed). The default Normal state is Open. Press
ENTER.
3. Connect contact wires (300 V-rated cabling required) to the terminal block on the user
connection plate. Use a 2.5-mm standard screwdriver.
4. Run the wires from the terminal block out the roof or under the floor of the PDU to your
contacts.
Note
You will be prompted for your password.
Warning
Ensure the wires are properly retained and kept away from
high-voltage lines and breakers.
See also
See the “Specifications” section in the InfraStruXure PDU Operation
and Configuration manual (990-1984) for relay output specifications.
Load-Meter
Volt-Meter
Contacts
Breakers
Alarms
Panel
Config
Help
>Contact Inputs
>Relay Outputs
>Alarm Relay Map
Contact In:01of04
Name: User Contact1
Normal:Open
Status: Closed