Specifications
150 kW InfraStruXure Power Distribution Unit 9
Electrical Requirements and Specifications
Electrical requirements
† Provided by customer. Copper conductors only!
‡ The specifications are recommendations only. Consult the NEC and local codes for requirements specific to your
installation.
480 V 600 V
Service distribution breaker
†‡
250 A 200 A
Conductors to main input breaker
†
3W + G + GEC 3W + G + GEC
Recommended wire sizing
‡
L1, L2, L3 4/0 AWG 3/0 AWG
G 4 AWG 6 AWG
GEC 2 AWG 4 AWG