Specifications
Symmetra PX 48, 96, and 160 kW 400 V and 100 kW 208 V Operation20
Replace a battery
.
1. Holding the handle, gently lift the battery unit and pull it halfway out.
2. Release the locking mechanism by lifting the battery unit. Pull the battery unit completely out
while supporting it.
3. Take the replacement battery unit and push it into the system.
Note: When replacing batteries, always replace both batteries A+B or C+D (see illustration
above).
Note: Allow batteries a 24-hour recharging period after system start-up/battery replacement
for battery monitoring data to become fully reliable.
Use two people to lift components weighing between 18–32 kg (40–70 lb).
Pxb0026a
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D