Specifications

11Symmetra PX 48, 96, and 160 kW 400 V and 100 kW 208 V Operation
4. Use the display interface to turn the UPS off.
5. Set the
UPS SYSTEM ENABLE
switch to the OFF
position.
6. Set the Q1 switch to the OFF
position.
7. Set the Q5 breaker to the OFF
position (if applicable).
8. Set the
DC DISCONNECT switch
to the OFF position on all XR
Battery Enclosures and the PDU-
XR (if applicable).
a. Select UPS and press ENTER. b. Select UPS Power Control and press ENTER.
c. Select Turn UP S O ff and press
ENTER. d. Select No, Don’t Notify and press ENTER.
e. Confirm by selecting YES, Turn UPS Off and
press
ENTER.
f. Wait for the UPS to turn off.
UPS
Alarms
Power Dist
Switch Gear
Environment
Log
Admin
Help
UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
Notify PowerChute?
Cancel
Yes, Notify Servers
No, Don’t Notify
Turn UPS Off Without
Server Notification?
>NO, ABORT
>YES, Turn UPS Off
Turning UPS off,
please wait...
UPS
100 kW
48/96/160 kW
XR Battery Enclosures/PDU-XR