Specifications

Symmetra PX 48, 96, and 160 kW 400 V and 100 kW 208 V Operation10
Transfer the UPS into maintenance bypass operation
1. Use the display to transfer the UPS in bypass.
Note: The H3 LED next to the Q3 switch will illuminate, indicating that it is ok to operate the
Q3 switch.
2. Set the Q3 switch to the ON position.
Note: The H2 LED beside the Q2 switch will illuminate, indicating that it is ok to operate the
Q2 switch.
3. Set the Q2 switch to the OFF position.
Note: If shutdown via the display is disabled, proceed to step five. If you want to enable
shutdown via the display, then call APC.
a. Select UPS and press ENTER. b. Select UPS Power Control and press ENTER.
c. Select UPS into Bypass and press
ENTER. d. Select Yes, Into Bypass and press ENTER.
e. Wait for the transfer to complete. f. Confirm that the transfer to bypass is complete.
UPS
Alarms
Power Dist
Switch Gear
Environment
Log
Admin
Help
UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
Confirm:
UPS into Bypass?
NO, ABORT
YES, Into Bypass
Putting UPS into
Bypass, please
wait...
UPS is now in
bypass.
Press any key...