Symmetra PX 48, 96, and 160 kW 400 V and 100 kW 208 V Operation8
3. Set the SYSTEM ENABLE switch on the UPS to the ON position.
Note: Wait approximately two minutes for the system to start.
4. Set the Q5 breaker to the ON position (if applicable).
Note: The H2 LED next to the Q2 switch will illuminate, indicating that it is safe to operate
the Q2 switch.
5. Set the Q2 switch on the PDU, PDU-XR or the external maintenance bypass panel to the ON
position.
6. Use the display interface to turn the UPS on:
a. Select UPS and press ENTER. b. Select UPS Power Control and press ENTER.
c. Select Turn UPS On and press
ENTER. d. Confirm by selecting Yes , Tu r n UP S On and
press
ENTER.
e. Wait for the UPS to turn the UPS on.