Specifications
Symmetra PX 48, 96, and 160 kW 400 V and 100 kW 208 V Operation6
Perform a total power off
Warning: This procedure will disconnect the load.
Warning: Verify that the UPS is in total power off mode by following this procedure.
Note: If shutdown via the display is disabled, proceed to step two. If you want to enable
shutdown via the display, then call APC.
1. Use the display interface to turn the UPS off.
2. Set the
UPS SYSTEM ENABLE
switch to the OFF
position.
3. Set the Q2 switch to the OFF
position.
4. Set the Q1 switch to the OFF
position.
5. Set the Q5 breaker to the OFF
position (if applicable).
6. Verify that the maintenance
bypass switch (Q3) is in the
OFF position.
a. Select UPS and press ENTER. b. Select UPS Power Control and press ENTER.
c. Select Turn UPS Off and press
ENTER. d. Select No, Don’t Notify to shut down without
delay and press
ENTER.
e. Confirm YES, Turn UPS Off and press
ENTER. f. Wait for the UPS to turn off.
UPS
Alarms
Power Dist
Switch Gear
Environment
Log
Admin
Help
UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
Notify PowerChute?
Cancel
Yes, Notify Servers
No, Don’t Notify
Turn UPS Off Without
Server Notification?
>NO, ABORT
>YES, Turn UPS Off
Turning UPS off,
please wait...