Operation Symmetra® PX 48, 96, and 160 kW 400 V 100 kW 208 V
About this Manual This manual is intended for users of: • Symmetra® PX 48 kW 400 V UPS • Symmetra® PX 96 and 160 kW 400 V UPS and Power Distribution Unit (PDU-XR) • Symmetra® PX 100 kW 208 V UPS and Power Distribution Unit (PDU) • XR Battery Enclosure It refers to important safety warnings and instructions, gives an introduction to the display interface, and provides information on operation and troubleshooting.
Contents Overview........................................................................... 1 User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Interface area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Display interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operation...............................................
Maintenance................................................................... 17 Parts Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Determine if you need a replacement part . . . . . . . . . . . . . . 17 Return parts to APC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Replace a power module . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Replace a battery . .
Overview User Interface Interface area Load Powered ESC Check Log ? Warning Critical LOAD POWERED LED When the LED is green, power to the load is on. When the LED is yellow, the load is supplied through the batteries. When the LED is flashing yellow, the unit is in bypass. CHECK LOG LED When the LED is green, a new event has been added to the event log. WARNING LED When the LED is yellow, there are one or more warning alarms in the system.
Display interface Overview screens. When the system is running, the display will scroll through screens showing information about the system and any active alarms. Note: The data values shown are for example only. No Active Alarms System Date/Time: 28-Mar-2010 10:37:01 Volts In L1: xxx L2: xxx L3: xxx Out L1: L2: L3: Volts L1: L2: L3: Amps xxx xxx xxx kW xx.x xx.x xx.x Out xxx xxx xxx kVA xx.x xx.x xx.x Symmetra PX 160 kW Runtime: xxhr xxmin Capacity xxx.
Menu tree Main Menu UPS Power Dist UPS Power Control Total Loading UPS Status UPS Tests & Diags UPS Configuration Modular Loading All Active Alarms Active by Severity Active by Type Environment Status Input Contacts Output Relays Factory Alarm Relay Map Volt-Meter Env Monitoring Card Subfeeds Log Alarms Switchgear Admin View New Log Items View Entire Log Clear Entire Log Help Network Setup Local Interface Date/Time Device IP Caution: Do not attempt to make any changes to screens that
Operation Operation Modes In an installation that does not include a maintenance bypass panel, the UPS has three operation modes. If the installation includes a PDU, a PDU-XR, or an external maintenance bypass panel, maintenance bypass operation also becomes available. Normal operation During normal operation, the UPS converts the utility/mains supply to conditioned power for the connected load.
Perform a total power off Warning: This procedure will disconnect the load. Warning: Verify that the UPS is in total power off mode by following this procedure. Note: If shutdown via the display is disabled, proceed to step two. If you want to enable shutdown via the display, then call APC. 1. Use the display interface to turn the UPS off. a. Select UPS and press ENTER. UPS Power Dist Switch Gear Environment b. Select UPS Power Control and press ENTER. Alarms Log Admin Help UPS UPS UPS UPS c.
7. Set the DC DISCONNECT switch on all of the XR Battery Enclosures and the PDU-XR (if applicable) to the OFF position. XR Battery Enclosures/PDU-XR 8. Disconnect all battery units by removing them or pulling them out to the red disconnect line. Caution: To ensure that the enclosure does not tip, do not pull out the battery units beyond the red disconnect line. If you intend to completely remove the battery units, remove them from the enclosure one at a time.
3. Set the SYSTEM ENABLE switch on the UPS to the ON position. 48/96/160 kW 100 kW UPS Note: Wait approximately two minutes for the system to start. 4. Set the Q5 breaker to the ON position (if applicable). Note: The H2 LED next to the Q2 switch will illuminate, indicating that it is safe to operate the Q2 switch. 5. Set the Q2 switch on the PDU, PDU-XR or the external maintenance bypass panel to the ON position. 6. Use the display interface to turn the UPS on: a. Select UPS and press ENTER.
Turn the UPS load off 1. Select UPS and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log Admin Help 3. Select Turn UPS Off and press ENTER. Turn UPS Off Reboot UPS UPS Into Bypass UPS To Sleep 5. Confirm YES, Turn UPS Off and press ENTER. Turn UPS Off Without Server Notification? >NO, ABORT >YES, Turn UPS Off 2. Select UPS Power Control and press ENTER. UPS UPS UPS UPS Power Control Status Tests & Diags Configuration 4. Select No, Don’t Notify and press ENTER.
Transfer the UPS into maintenance bypass operation 1. Use the display to transfer the UPS in bypass. a. Select UPS and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log Admin Help c. Select UPS into Bypass and press ENTER. Turn UPS Off Reboot UPS UPS into Bypass UPS to Sleep e. Wait for the transfer to complete. Putting UPS into Bypass, please wait... b. Select UPS Power Control and press ENTER. UPS UPS UPS UPS Power Control Status Tests & Diags Configuration d.
4. Use the display interface to turn the UPS off. a. Select UPS and press ENTER. UPS Power Dist Switch Gear Environment b. Select UPS Power Control and press ENTER. Alarms Log Admin Help UPS UPS UPS UPS c. Select Turn UPS Off and press ENTER. d. Select No, Don’t Notify and press ENTER. Notify PowerChute? Cancel Yes, Notify Servers No, Don’t Notify Turn UPS Off Reboot UPS UPS into Bypass UPS to Sleep e. Confirm by selecting YES, Turn UPS Off and press ENTER. f. Wait for the UPS to turn off.
Return to on line operation from maintenance bypass operation 1. Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the PDU-XR (if applicable). 2. Set the Q1 switch to the ON position. 3. Set the SYSTEM ENABLE switch on the UPS to the ON position. 48/96/160 kW 100 kW UPS Note: Wait approximately two minutes for the system to start. 4. Set the Q5 breaker to the ON position (if applicable).
5. Use the display interface to turn the UPS load on: a. Select UPS and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log Admin Help c. Select Turn UPS On Into Bypass and press ENTER. Turn UPS On UPS On Into Bypass e. Confirm by selecting Yes, On Into Bypass and press ENTER. Confirm: UPS on Into Bypass >NO, ABORT >Yes, On Into Bypass b. Select UPS Power Control and press ENTER. UPS UPS UPS UPS Power Control Status Tests & Diags Configuration d. Select Continue Turn On and press ENTER.
8. Use the display interface to transfer the UPS out of bypass: n: a. Select UPS and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log Admin Help c. Select UPS out of Bypass and press ENTER. Turn UPS of Reboot UPS UPS out of Bypass UPS to Sleep e. Wait for the UPS to transfer out of bypass. Putting UPS out of Bypass, please wait... b. Select UPS Power Control and press ENTER. UPS UPS UPS UPS Power Control Status Tests & Diags Configuration d.
Configuration System Settings Set up the network 1. Select Admin and press ENTER. UPS Power Dist Switchgear Environment Alarms Log Admin Help 3. Select Mode and press ENTER. Stat: Mode: IP: SM: 2. Select Network Setup and press ENTER. Network Setup Local Interface Date/Time Device ID 4. Select Fixed IP Addr to give a specific IP adress to the UPS system or select one of the other three methods to obtain an IP adress. In this example Fixed IP Addr mode is selected.
Change the date and time 1. Select Admin and press ENTER. UPS Power Dist Switchgear Environment Alarms Log Admin Help 2. Select Date/Time and press ENTER. Network Setup Local Interface Date/Time Device ID 3. Select Date or Time and change the settings by using the UP and DOWN arrow keys. Press ENTER to save the changes. Mode: Manual Format: mm/dd/yyyy Date: xx/xx/xxxx Time: xx:xx:xx Configure input contacts 1. Select Environment and press ENTER.
Maintenance Parts Replacement Determine if you need a replacement part To determine if you need a replacement part, contact APC Customer Support and follow the procedure below so that the APC Customer Support representative can assist you promptly: 1. In the event of a module failure, the display interface may show additional “fault list” screens. Press any key to scroll through these fault lists, record the information, and provide it to the representative. 2.
Replacement parts Warning: All safety instructions in the Safety sheet (990-2984) should be read, understood, and followed prior to handling the system. Failure to do so could result in equipment damage, serious injury, or death. Warning: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. Note: A maximum of two SmartSlots may be used. Part APC Part No.
Replace a power module Warning: Before removing any power modules, make sure that the remaining power modules can support the load. Use two people to lift components weighing between 18–32 kg (40–70 lb). 1. Turn the locking latch until the arrow points down. 2. Unscrew the spring-activated knobs on both sides of the module. 3. Pull the module up and out of the enclosure as far as the lock mechanism will allow. 4. Release the lock by pressing the black plastic tab on both sides of the module.
Replace a battery . Use two people to lift components weighing between 18–32 kg (40–70 lb). A B A B C D A B C D A B C D D Pxb0026a C 1. Holding the handle, gently lift the battery unit and pull it halfway out. 2. Release the locking mechanism by lifting the battery unit. Pull the battery unit completely out while supporting it. 3. Take the replacement battery unit and push it into the system.
Replace a power distribution module 48 kW 96 and 160 kW 100 kW 1. Switch the breakers to the OFF position. 2. Disconnect the power distribution module’s cable from the load. 3. Open the locking latch on the module and gently pull the module out of the enclosure. 4. Take the replacement power distribution module and open the locking latch. Route the power cable through the top of the enclosure and slide the power distribution module into place. 5. Secure the latch to lock the module. 6.
Troubleshooting Warning: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. UPS Alarms This section lists all of the common alarm and status messages that might be displayed on the display interface. A suggested corrective action is listed with each message to help troubleshoot the problem.
Display Message Meaning Corrective Action External Switch Gear The system no longer detects an Option 1: Ensure the external switch gear Communication Card Removed external switch gear communication communication card is installed properly. card. Option 2: Contact APC Customer Support. Graceful Shutdown Initiated A graceful shutdown or reboot has been initiated from the display interface or other accessory. No corrective action necessary.
Display Message Meaning Corrective Action Not Synchronized Fault System cannot synchronize to AC line and bypass mode may not be available. Option 1: Decrease the sensitivity to input frequency. Option 2: Correct the input voltage to provide acceptable voltage/frequency. Output Voltage Not In Range The output voltage is not within the specified range. Evaluate the threshold setting. If necessary, adjust it for your situation. Contact APC Customer Support.
Display Message Meaning Corrective Action Site Wiring Fault There is a problem with the phase rotation or a phase is missing in the input voltage to the UPS. Contact the certified electrician that installed the system. Static Bypass Switch Module Fault The static bypass switch module has Contact APC Customer Support. failed and requires replacement. Static Bypass Switch Module Removed The system no longer detects a static Option 1: Ensure the static bypass switch bypass switch module.
Modular Distribution Fault List The display interface will identify the number of the power distribution module that has caused an alarm or warning. Display Message Meaning Corrective Action High Module Current The threshold of the high module Evaluate the threshold setting. If necessary, adjust current has been exceeded. it for your situation. High Subfeed Current The threshold of the high subfeed current has been exceeded.
PDU Fault List Display Message Meaning Maintenance Bypass Alarm The system is in maintenance bypass: the Q2 switch is open and the Q3 switch is closed. Output V Voltage Under Limit 28 Corrective Action No corrective action necessary. Phase-to-neutral output voltage Evaluate the threshold setting. If necessary, for phase has dropped adjust it for your situation. below the configured limit. Output V Voltage Over Limit Phase-to-neutral output voltage Evaluate the threshold setting.
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support.