Operation Manual Smart-UPS™ C Uninterruptible Power Supply 1000/1500 VA Rack-Mount 2U 120/230 Vac su00 812a
Product Description The APC™ by Schneider Electric Smart-UPS™ is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from AC power blackouts, brownouts, sags, and surges, small AC fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until AC power returns to safe levels or the batteries are fully discharged. Safety and General Information Inspect the package contents upon receipt.
Product Overview Front panels 1000VA 120/230 Vac 1 Display interface 2 Bezel su05 63c 3 Battery 4 Internal battery connector 1500 VA 120/230 Vac s u0 6 30c Rear panels su0644d 1000 VA 230 Vac su0644c 1000 VA 120 Vac 1500 VA 120 Vac 2 su0644e su0644b 1500 VA 230 Vac 1 UPS input 4 Outlets 2 Circuit breaker/Overload protection 5 USB port 3 Chassis ground connection screw (GND) 6 Serial data port Smart-UPS C 1000/1500 VA 120/230 Vac Rack-Mount 2U
Installation For UPS installation information, refer to the Installation Guide for the Smart-UPS C 1000/1500 VA Rack-Mount 2U included with the UPS. The Installation Guide is also available on the Documentation CD included with the UPS and on the APC Web site, www.apc.com. Operation Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period. 1. Connect equipment to the UPS. su0628b 2.
Power saving LCD screen The display interface can be configured to remain continuously illuminated or to extinguish after a period of inactivity to save electricity. 1. Continuous Illumination Mode: Press and hold the DISPLAY button for two seconds. The display will illuminate and the UPS will beep to confirm Continuous Illumination mode is activated. 2. Power Saving mode: Press and hold the DISPLAY button for two seconds.
Status Indicators Display panel features 1000/1500 VA 230 Vac su0740b su0740c 1000/1500 VA 120 Vac 1 On Line/On Battery LED 4 Display interface 2 POWER ON/O FF button 5 DISPLAY button 3 Site Wiring/System Fault LED 6 MUTE button Note: Refer to Feature Reference Guide on page 8 in this manual for a detailed description of the front panel buttons and icons.
LCD status indicators Status LCD Icon Audible Alarms Beeps 4 times every 30 seconds. Audible Alarm Terminates The beeping stops when AC power is restored or the UPS is turned off. AC Power Overload An overload condition has occurred while the UPS is operating on AC power. Constant tone The alarm stops when nonessential equipment is disconnected from the outlets or the UPS is turned off Battery Power Overload An overload condition has occurred while the UPS is operating on battery power.
Display interface features 1000/1500 VA 120 Vac 1000I/1500I VA 230 Vac Description On Line: The UPS is supplying conditioned AC power to connected equipment. Green mode: The UPS is operating at the most efficient level by bypassing unused AVR components while acceptable AC voltage is present. The UPS will enter and exit Green mode automatically and will not compromise power protection. Load Capacity: The load capacity percentage is indicated by the number of load bar sections illuminated.
System Faults 1000/1500 230 Vac su0752b su0752a 1000/1500 120 Vac P00 Output Overload P01 Output Short Circuit P02 Output Over Voltage P04 Unit Over Temperature P06 AVR Relay Fault P13 Inverter Fault Note: Refer to the "Feature Reference Guide" on page 8 for a detailed description of the front panel buttons and icons. For more information on System Faults, contact customer support at the APC Web site, www.apc.com/support.
Troubleshooting Problem and Possible Cause Solution The UPS will not turn on or there is no output. The UPS has not been turned on. Press the ON button once to turn on the UPS. The UPS is not connected to AC power. Be sure the power cable is securely connected to the UPS and to the AC power supply. The input circuit breaker has tripped. Disconnect nonessential equipment and reset the circuit breaker. The UPS shows very low or no AC input voltage.
Battery Replacement Always recycle used batteries. For information on recycling a used battery, refer to the Battery Disposal Information sheet included with the replacement battery. Replace used batteries with APC approved batteries. To order a replacement battery go to the APC Web site, www.apc.com. UPS Model SMC1000-2U/SMC1000I-2U APCRBC124 Replacement Battery SMC1500-2U/SMC1500I-2U APCRBC132 Service If the unit requires service, do not return it to the dealer. Follow these steps: 1.
Two-Year Factory Warranty This warranty applies only to the products you purchase for your use in accordance with this manual. Terms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. APC will repair or replace defective products covered by this warranty. This warranty does not apply to equipment that has been damaged by accident, negligence or misapplication or has been altered or modified in any way.
12 Smart-UPS C 1000/1500 VA 120/230 Vac Rack-Mount 2U
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support.