Install Instructions
16
GAS CONNECTIONS
 WARNING
THE INLET GAS PRESSURE MUST NOT EXCEED THE VALUE 
SPECIFIED BY THE MANUFACTURER ON THE RATING 
PLATE (10.5” W.C. - NATURAL GAS, 13.0” W.C. - PROPANE 
GAS).  EXPOSURE  TO  HIGHER  GAS  SUPPLY  PRESSURE 
MAY CAUSE DAMAGE TO THE GAS VALVE WHICH COULD 
RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS 
OCCURRED SUCH AS THROUGH IMPROPER TESTING 
OF GAS LINES OR EMERGENCY MALFUNCTION OF THE 
SUPPLY SYSTEM, THE GAS VALVE MUST BE CHECKED 
FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE 
VENTS ON THE SUPPLY REGULATORS AND THE SAFETY 
VENT VALVES ARE PROTECTED AGAINST BLOCKAGE.  
THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT 
THE HEATER. VENT BLOCKAGE MAY OCCUR DURING ICE 
STORMS.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE 
FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH 
FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR 
EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST 
BE INTERNALLY TINNED AND CERTIFIED FOR GAS 
SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS 
PIPE IS CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS 
SUPPLY LINE, A SEDIMENT TRAP MUST BE INCORPORATED 
IN THE PIPING. SEE PIPING DIAGRAMS. THE SEDIMENT 
TRAP MUST BE READILY ACCESSIBLE AND NOT SUBJECT 
TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH 
THE CURRENT EDITION OF ANSI Z223.1 OF THE NATIONAL 
FUEL GAS CODE.
To prevent damage, care must be taken not to apply too 
much torque when attaching gas supply pipe to gas valve 
gas inlet.
Fittings and unions in the gas line must be metal to metal type.
Apply  joint  compounds  (pipe  dope)  sparingly  and  only  to  the 
male threads of pipe joints. Do not apply compound to the rst 
two threads. Use compounds resistant to the action of liqueed 
petroleum gases.
BEFORE PLACING THE HEATER IN OPERATION, CHECK 
FOR GAS LEAKAGE. Use soap and water solution or other 
material  acceptable for the purpose in locating gas leaks. 
DO NOT USE MATCHES, CANDLES, FLAME OR OTHER 
SOURCES OF IGNITION FOR THIS PURPOSE.
DISCONNECT THE HEATER AND ITS MANUAL GAS 
SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM 
DURING ANY PRESSURE TESTING OF THAT SYSTEM AT 
TEST  PRESSURES  IN  EXCESS  OF  1/2  PSIG.  THE  GAS 
SUPPLY LINE MUST BE CAPPED WHEN NOT CONNECTED 
TO HEATER.
THE HEATER MUST BE ISOLATED FROM THE GAS SUPPLY 
PIPING SYSTEM BY CLOSING ITS MANUAL GAS SHUTOFF 
VALVE DURING ANY PRESSURE TESTING OF THE GAS 
SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO 
OR LESS THAN 1/2 PSIG (3.44kPa).
CORRECT GAS
MAKE SURE the gas on which the heater will operate is the 
same as that specied on the heater model and rating plate. Do 
not install the heater if equipped for a different type gas - contact 
the heater supplier.
SIZING GAS SUPPLY LINE
The iron pipe or equivalent pipe sizes in Table 6 are 
derived from Table C-3 in the NATIONAL FUEL GAS CODE. 
The pipe sizes are based on a supply line gas pressure 
drop of 0.3 inches of water column from the gas meter to 
the point of installation of the heater(s). For natural gas, 
a  heating  value  of  1050  Btu/ft
3
 and a specific gravity of 
0.60 has been assumed. A heating value  of  2500  Btu/ft
3
and a specific gravity of 1.53 has been assumed for L.P. 
(propane) gas.
Where it is necessary to use an excess number of pipe ttings, i.e., 
elbows, tees and valves, in the gas supply line, use pipe at least 
one size larger than that recommended in Table 6 to compensate 
for the increased pressure drop.
If the service pressure is 4.5 inches W.C. (1.12kPa) for natural 
gas or (11 inches (1.74kPa) for L.P. gas) of water column or 
less, use pipe size larger than specified in Table 6 to minimize 
pressure drop in the line.
GAS METER SIZE - City Gases Only
Be sure that the gas meter has sufcient capacity to supply the 
full rated gas input of the heater as well as the requirements of 
all other gas red equipment supplied by the meter. If gas meter 
is too small, ask the gas company to install a larger meter having 
adequate capacity.
 TABLE 6
 GAS SUPPLY PIPE SIZES (IN INCHES)
     NATURAL GAS (1050 Btu/ft
3
)     PROPANE GAS (2500 Btu/ft
3
)
 Distance To Heater   
 From Meter (FT./M)  HW-120M  HW-160M  HW-200M  HW-225M  HW-120M  HW-160M  HW-200M
  10 (3M)  1/2  3/4  3/4  3/4  1/2  1/2  1/2
  30 (9.1M)  3/4  3/4  1  1  1/2  3/4  3/4
  50 (15.2M)  3/4  1  1  1  3/4  3/4  1
  80 (24.4M)  1  1  1 1/4  1 1/4  3/4  1  1
  100 (30.5M)  1  1 1/4  1 1/4  1 1/4  3/4  1  1
  150 (45.7M)  1  1 1/4  1 1/4  1 1/4  1  1  1 1/4
  200 (61M)  1 1/4  1 1/4  1 1/4  1 1/2  1  1 1/4  1 1/4










