Install Instructions
11
CONFINED SPACE
When drawing combustion and dilution air from inside a 
conventionally constructed building to a conned space, such a 
space shall be provided with two permanent openings, ONE IN OR 
WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE TOP AND 
ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE 
BOTTOM. Each opening shall have a free area of at least one 
square inch per 1000 Btuh (2,225mm
2
/Kw) of the total input of all 
appliances in the enclosure, but not less than 100 square inches 
(645 square cm).
If  the  conned  space  is  within  a  building  of  tight  construction, 
air for combustion, ventilation and draft hood dilution must be 
obtained from outdoors. When directly communicating with the 
outdoors or communicating with the outdoors through vertical 
ducts, two permanent openings, located in the above manner, 
shall be provided. Each opening shall have a free area of not less 
than one square inch per 4000 Btuh (8,900mm
2
/Kw) of the total 
input of all appliances in the enclosure. If horizontal ducts are 
used, each opening shall have a free area of not less than one 
square inch per 2000 Btuh (4,450mm
2
/Kw) of the total input of all 
appliances in the enclosure. For Canadian installations consult 
CAN/CGA B149.
Where an exhaust fan is installed in the same room with a 
heater, sufcient openings for air must be provided in the walls.  
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN 
INTO THE ROOM THROUGH THE CHIMNEY, CAUSING 
POOR COMBUSTION. SOOTING MAY RESULT AND RISK OF 
ASPHYXIATION WILL OCCUR.
VENTING
In the United States:
Vent sizing, installation and termination shall be in accordance with 
current edition of the NATIONAL FUEL GAS CODE. ANSI Z223.1.
Remove all soot or other obstructions from chimney which will 
retard free draft.
1.  Install and size the vent pipe as necessary. The connection from 
the heater to the chimney should be run full size and should 
have a minimum pitch upward to the chimney of one quarter 
inch per foot length.
PROPER VENT PIPE INSTALLATION
FIGURE 6
  Do not install without draft hood and do not install any damper 
in ueway. Be sure that the vent pipe does not extend beyond 
the inside wall of the chimney.
2.  Where a continuous or intermittent back draft is found to exist, 
the cause must be determined and corrected. A special vent 
cap may be required.
  FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR 
CONTAMINATION AND UNSAFE CONDITIONS.
•  If the back draft cannot be corrected by the normal methods  
or  if  a suitable  draft cannot  be  obtained,  a  blower type  ue 
gas exhauster must be employed to assure proper venting and 
correct combustion.
3.  Do not connect the heater to a common ue or chimney with 
solid fuel burning equipment. This practice is prohibited by 
many local building codes as is the practice of venting gas red 
equipment to the duct work of ventilation systems.
•  Where a separate vent connection is not available and the vent 
pipe from the heater must be connected to a common ue with an 
oil burning furnace, the vent pipe should enter the common ue 
or chimney at a point above the ue pipe from oil furnace.
4. Where two or more appliances vent into a common vent 
connector or manifold, the area of the common vent should at 
least equal the area of the largest ue or vent connector plus 
50% of the areas of the additional draft hood outlets.
5.  Refer to the National Fuel Gas Code for information pertaining 
to multiple heater venting. The ASHRAE HVAC SYSTEMS &  
EQUIPMENT HANDBOOK, as well as many manufacturers’ 
gas vent and chimney sizing handbooks contain information 
on multiple heater manifold venting.
RELIEF VALVE
An ASME-rated pressure relief valve (Supplied) must be installed 
in the hot water outlet line as near to the heater as possible. This 
pressure relief valve is rated in accordance with and complies with 
the current edition of the ANSI/ASME Boiler and Pressure Vessel 
Code, Section IV.
A CSA design-certied and ASME-rated temperature and pressure 
relief valve (Not Supplied) must be installed on each and every water 
storage tank. This relief valve shall comply with the Standard for 
Relief Valves for Hot Water Supply systems, “ANSI Z21.22 current 
edition”. This relief valve should have a temperature rating of 210°F 
(98.8°C), a pressure rating not exceeding the lowest rated working 
pressure of any system component and a discharge capacity 
exceeding the total input of the water heaters supplying water to 
the storage tank.
Select a relief valve with a discharge capacity exceeding the 
maximum heater input rating and a pressure rating not exceeding 
the working pressure shown on the rating plate of the heater.
Locate the T & P relief valve in the top of the tank, or in the side 
of the tank on centerline within the upper 6 inches from the top of 
the tank. See installation diagrams. Tapping shall be threaded 
in accordance with the latest version of the Standard for Pipe 
Threads,  General  Purpose  (inch), ANSI/ASME  B1.20.1.  Mark 
location with a Class III label.










