Product Overview

Commercial Gas
Water Heaters
Page 2 of 6
AOSCG10215
VENT REQUIREMENTS FOR BTHL 150A - 250A
VENT REQUIREMENTS FOR BTHL 300A - 500A
GAS PRESSURE REQUIREMENTS
OTHER FEATURES:
SPACE-SAVING DESIGN FOR INSTALLATION FLEXIBILITY
Large volume, integrated solution eliminates need for multiple
100-gallon water heaters or separate storage tank
Easy-to-remove top cover for convenient access to serviceable parts
0˝ installation clearances on sides and rear, 1-1/2˝ installation
clearance on top
Handhole cleanout allows easy access to tank interior for cleaning
0˝ clearance to combustibles, approved for installation on
combustible floors
CODES AND STANDARDS
CSA certified and ASME rated T&P relief valve
Maximum hydrostatic working pressure: 160 psi
All models are design certified by Underwriters Laboratories (UL),
Inc., to ANSI Z21.10.3 - CSA 4.3 Standards
Meets the thermal efficiency and standby loss requirements of the
U.S. Department of Energy and current edition ASHRAE/IES 90.1
Design Certified by Underwriters Laboratories to NSF standard 5 for
180°F (62°C) water
Complies with SCAQMD Rule 1146.2 and other Air Quality
Management Districts with similar requirements for ultra low-NOx
emissions
ASME tank construction standard on all model sizes
Depending on the installed equivalent length, and/or the number of appliances connected, the supply gas line size may need to be increased beyond the minimum required size.
Model Number
Manifold Pressure Minimum Supply Pressure Maximum Supply Pressure
Natural Gas Propane Gas Natural Gas Propane Gas Natural Gas Propane Gas
BTHL-150A 0" W.C. (0 kPa) 0" W.C. (0 kPa) 3.5" W.C. (1.10 kPa) 8.5" W.C. (2.12 kPa) 14" W.C. (3.49 kPa) 14" W.C. (3.49 kPa)
BTHL-199A 0" W.C. (0 kPa) 0" W.C. (0 kPa) 3.5" W.C. (1.10 kPa) 8.5" W.C. (2.12 kPa) 14" W.C. (3.49 kPa) 14" W.C. (3.49 kPa)
BTHL-250A 0" W.C. (0 kPa) 0" W.C. (0 kPa) 3.5" W.C. (1.10 kPa) 8.5" W.C. (2.12 kPa) 14" W.C. (3.49 kPa) 14" W.C. (3.49 kPa)
BTHL-300A 0" W.C. (0 kPa) 0" W.C. (0 kPa) 4.8" W.C. (1.19 kPa) 8.5" W.C. (2.12 kPa) 14" W.C. (3.49 kPa) 14" W.C. (3.49 kPa)
BTHL-400A 0" W.C. (0 kPa) 0" W.C. (0 kPa) 4.8" W.C. (1.19 kPa) 8.5" W.C. (2.12 kPa) 14" W.C. (3.49 kPa) 14" W.C. (3.49 kPa)
BTHL-500A 0" W.C. (0 kPa) 0" W.C. (0 kPa) 4.8" W.C. (1.19 kPa) 8.5" W.C. (2.12 kPa) 14" W.C. (3.49 kPa) 14" W.C. (3.49 kPa)
Number of 90°
Elbows Installed
3 Inch Pipe 4 Inch Pipe
Maximum Feet (Meters) Maximum Feet (Meters)
One (1) 45 feet (13.7 meters) 115 feet (35 meters)
Two (2) 40 feet (12.2 meters) 110 feet (33.5 meters)
Three (3) 35 feet (10.7 meters) 105 feet (32 meters)
Four (4) 30 feet (9.1 meters) 100 feet (30.5 meters)
Five (5) N/A 95 feet (29 meters)
Six (6) N/A 90 feet (27.4 meters)
Number of 90°
Elbows Installed
4 Inch Pipe 6 Inch Pipe
Maximum Feet (Meters) Maximum Feet (Meters)
One (1) 65 feet (19.8 meters) 115 feet (35 meters)
Two (2) 60 feet (18.2 meters) 110 feet (33.5 meters)
Three (3) 55 feet (16.8 meters) 105 feet (32 meters)
Four (4) 50 feet (15.2 meters) 100 feet (30.5 meters)
Five (5) 45 feet (13.7 meters) 95 feet (29 meters)
Six (6) 40 feet (12.2 meters) 90 feet (27.4 meters)