Installation Manual
Table Of Contents
- Safe Installation, Use and Service
- APPROVALS
- General Safety Information
- Introduction
- Features And Components
- Installation Considerations
- Installation Requirements
- Gas Pressure Requirements
- Supply Gas Line
- Supply Gas Regulator
- Power Supply
- Mixing Valves
- Dishwashing Machines
- Closed Water Systems
- Thermal Expansion
- Temperature-Pressure Relief Valve
- Condensate Drain
- Combustible Material Storage
- Contaminated Air
- Air Requirements
- Unconfined Space
- Confined Space
- Fresh Air Openings For Confined Spaces
- Outdoor Air Through Two Openings
- Outdoor Air Through One Opening
- Outdoor Air Through Two Horizontal Ducts
- Outdoor Air Through Two Vertical Ducts
- Air From Other Indoor Spaces
- Installation Requirements - Commonwealth of Massachusetts
- Venting Installation
- General Venting Information
- General Venting Instructions
- Venting Requirements
- Venting Installation Sequence
- Power Vent Installation
- Direct Vent Installation
- Vertical Termination Installation
- Sidewall Termination Installation
- Polypropylene Installations
- AL29-4C Vent Installations
- Concentric Termination Installation
- 6 Inch Concentric Termination Installation
- Low Profile Vent Installation
- Water Heater Installation
- Temperature Regulation
- Control System Operation
- Start Up
- Troubleshooting
- Maintenance
- Diagrams
- Notes
- Limited Warranty
44
OPERATING STATES
The current operational state of the water heater is displayed on the Desktop screen as the "Status." The common operational states
are described in the table below. See Figure 54 on page 55 and the Sequence Of Operation on page 54.
TABLE 17
State Description
Standby The water heater is not in an active heating cycle. IE: the Tank Temperature is at or above the Operating Set Point.
Input Verication The control system is conducting a diagnostic check at the beginning of a heating cycle.
Short Cycle Delay
The control system is waiting for a pre-dened time period to expire before initiating a heating cycle. This prevents "short-
cycling" which can greatly accelerate wear on components such as the Spark Igniter and Combustion Blower.
NOTE: If the control system is in this operational state increase the Differential setting in the Temperatures menu to
lengthen heating cycles.
Pre-Purge The Combustion Blower is energized to ush residual ue gases from the combustion chamber prior to ignition.
Spark Igniter
Energized
The Spark Igniter is energized.
Ignition Activation The 24 VAC Gas Valve is energized and opens to allow fuel gas to ow to the Main Burner.
Ignition Verication
The control system is monitoring the ame sensor for the required minimum ame sensing current.
See the Sequence Of Operation on page 54 for minimum ame sensing current (DC micro amps) information.
Inter-Purge The Combustion Blower is energized to ush residual fuel gas from the combustion chamber after a failed ignition attempt.
Heating Ignition was successful, ame sensing current has been established. The water in the storage tank is being heated.
Post-Purge
The Combustion Blower is energized to ush residual ue gases from the combustion chamber at the end of a heating
cycle.
Fault
The control system has detected a Fault condition. Heating operation is disabled until the Fault condition is corrected.
Power to the water heater must be cycled off and on at the breaker to reset the control system.
NOTE: Cycling power will not reset the control system if the condition that caused the Fault has not been corrected.
CONTROL SYSTEM MENUS
From the Desktop screen pressing the Operational directly below "Menu" on the LCD will display the "Main Menu" this is where all
control system menus are located. The table below describes the control system menus.
TABLE 18
Menu Description
Temperatures Most commonly accessed menu. Contains the Operating Set Point and Differential user settings.
Heater Status This menus displays the current state of all pressure switches and the ECO (open/closed). The on/off status of the
Combustion Blower, gas valve, spark igniter, ame sensor and other monitored water heater components are displayed
in this menu.
Display Settings Temperature units (°F or °C), the LCD appearance (brightness/contrast) and backlight delay user adjustable settings
are located in this menu.
Heater Information Elapsed time of operation, total heating cycle time, heating cycle count, heating on time along with UIM and CCB
software revisions can be viewed in this menu.
Current Fault Displays any current Alert or Fault messages.
Fault History This control system menu retains a list of the last nine (9) Fault and Alert messages with a time stamp. The newest
event will replace the oldest. Faults will clear after 30 days.
Fault Occurrence This control system menu retains a running total of how many times each Fault condition has occurred since the water
heater was rst installed. This screen does not clear and the information can not be reset.
Restore Factory Defaults This control system feature allows the user to restore control system user settings to their factory default settings.
Display Settings preferences ARE NOT changed when factory defaults are restored.
Help Screens Text based operational and user information explaining how to change user settings, navigate the control system menus
and icon descriptions.