Specification Sheet

Commercial Gas
Water Heaters
Page 5 of 6
AOSCG10210
GAS LINE CONNECTION SIZESTORAGE CAPACITY
RECOVERY CAPACITY
Model Series Natural Gas Propane Gas
BTH 120 300/301 3/4" NPT 3/4" NPT
BTH 150 300/301 3/4" NPT 3/4" NPT
BTH 199 300/301 3/4" NPT 3/4" NPT
BTH 250 300/301 3/4" NPT 3/4" NPT
BTH 300 300/301 1-1/2" NPT 1-1/2" NPT
BTH 400 300/301 1-1/2" NPT 1-1/2" NPT
BTH 500 300/301 1-1/2" NPT 1-1/2" NPT
Model Number Type of Gas
Input
Thermal
Efficiency
BTU/HR kW
BTH-120(A) Natural/Propane 120,000 35 95%
BTH-150(A) Natural/Propane 150,000 44 98%
BTH-199(A) Natural/Propane 199,900 58 97%
BTH-250(A) Natural/Propane 250,000 73 96%
BTH-300(A) Natural/Propane 300,000 88 96%
BTH-400(A) Natural/Propane 399,900 117 95%
BTH-500(A) Natural/Propane 499,900 146 95%
Model
Number
U.S. GALLONS/HR AND LITRES/HR AT TEMPERATURE RISE INDICTATED
Approx.
Capacity
°F 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F
°C 17°C 22°C 28°C 33°C 39°C 44°C 50°C 56°C 61°C 67°C 72°C 78°C
BTH-120(A)
60 U.S. Gals. GPH 461 345 276 230 197 173 154 138 126 115 106 99
227 Litres LPH 1743 1308 1046 872 747 654 581 523 475 436 402 374
BTH-150(A)
100 U.S. Gals. GPH 594 445 356 297 255 223 198 178 162 148 137 127
379 Litres LPH 2248 1686 1349 1124 963 843 749 674 613 562 519 482
BTH-199(A)
100 U.S. Gals. GPH 783 588 470 392 336 294 261 235 214 196 181 168
379 Litres LPH 2965 2224 1779 1483 1271 1112 988 890 809 741 684 635
BTH-250(A)
100 U.S. Gals. GPH 970 727 582 485 416 364 323 291 264 242 224 208
379 Litres LPH 3670 2753 2202 1835 1573 1376 1223 1101 1001 918 847 786
BTH-300(A)
119 U.S. Gals. GPH 1164 873 698 582 499 436 388 349 317 291 269 249
450.96 Litres LPH 4405 3304 2643 2202 1888 1652 1468 1321 1201 1101 1017 944
BTH-400(A)
119 U.S. Gals. GPH 1535 1151 921 767 658 576 512 460 419 384 354 329
450.96 Litres LPH 5810 4358 3486 2905 2490 2179 1937 1743 1585 1453 1341 1245
BTH-500(A)
119 U.S. Gals. GPH 1919 1439 1151 959 822 720 640 576 523 480 443 411
450.96 Litres LPH 7263 5448 4358 3632 3113 2724 2421 2179 1981 1816 1676 1556
Model Number U.S. Gallons Liters
BTH 120 60 227
BTH 150 100 379
BTH 199 100 379
BTH 250 100 379
BTH 300 119 450.96
BTH 400 119 450.96
BTH 500 119 450.96
Recovery capacities are based on AHRI rated thermal efficiencies.
For ASME Construction add an “A” to the end of the model number ex: BTH-120A.