Submittal Sheet

MODEL
TYPE
OF GAS
INPUT
THERMAL
EFFICIENCY
U.S. GALLONS/HR AND LITRES/HR AT TEMPERATURE RISE INDICATED
APPROX.
CAPACITY
ºF 30º F 40º F 50º F 60º F 70º F 80º F 90º F 100º F 110º F 120º F 130º F 140º F
BTU/HR kW ºC 17º C 22º C 28º C 33º C 39º C 44º C 50º C 56º C 61º C 67º C 72º C 78º C
BTH-120(A)
NATURAL/
PROPANE
120,000 35 95%
60 U.S. Gals.
GPH
461 345 276 230 197 173 154 138 126 115 106 99
227 Litres
LPH
1744 1308 1046 872 747 654 581 523 476 436 402 374
BTH-150(A)
NATURAL/
PROPANE
150,000 44 98%
100 U.S. Gals.
GPH
594 445 356 297 255 223 198 178 162 148 137 127
379 Litres
LPH
2248 1686 1349 1124 964 843 749 674 613 562 519 482
BTH-199(A)
NATURAL/
PROPANE
199,900 58 97%
100 U.S. Gals.
GPH
783 588 470 392 336 294 261 235 214 196 181 168
379 Litres
LPH
2965 2224 1779 1483 1271 1112 988 890 809 741 684 635
BTH-250(A)
NATURAL/
PROPANE
250,000 73 96%
100 U.S. Gals.
GPH
970 727 582 485 416 364 323 291 264 242 224 208
379 Litres
LPH
3671 2753 2202 1835 1573 1377 1224 1101 1001 918 847 787
BTH-300(A)
NATURAL/
PROPANE
300,000 88 96%
119 U.S. Gals.
GPH
1164 873 698 582 499 436 388 349 317 291 269 249
451 Litres
LPH
4405 3304 2643 2202 1888 1652 1468 1321 1201 1101 1017 944
BTH-400(A)
NATURAL/
PROPANE
399,900 117 95%
119 U.S. Gals.
GPH
1535 1151 921 767 658 576 512 460 419 384 354 329
451 Litres
LPH
5810 4358 3486 2905 2490 2179 1937 1743 1585 1453 1341 1245
BTH-500(A)
NATURAL/
PROPANE
499,900 146 95%
119 U.S. Gals.
GPH
1919 1439 1151 959 822 720 640 576 523 480 443 411
451 Litres
LPH
7263 5448 4358 3632 3113 2724 2421 2179 1981 1816 1676 1556
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Commercial Gas Water Heaters
Page 4 of 4
www.hotwater.com ©2014 A. O. Smith Corporation. All Rights Reserved
AOSCG10210
SUGGESTED SPECIFICATION
(Natural or Propane) gas water heater(s) shall be A. O. Smith Cyclone Mxi model # _________ or equal, minimum 95% thermal efficiency, a storage capacity of ______ gallons, an input rating of __________ BTUs
per hour, a recovery rating of ___________ gallons per hour (gph) at 100°F rise and a maximum hydrostatic working pressure of 160 PSI. Water heater(s) shall: 1. Modulating gas burner that automatically adjusts
the input based on demand. 2. Powered anodes that are non sacrificial and maintenance free. 3. Have seamless glass-lined steel tank construction, with glass lining applied to all water-side surfaces after the tank
has been assembled and welded; 4. Meets the thermal efficiency and/or standby loss requirements of the U. S. Department of Energy and current edition of ASHRAE/IESNA 90.1; 5. Have foam insulation and a
CSA Certified and ASME rated T&P relief valve; 6. Have a down-fired power burner designed for precise mixing of air and gas for optimum efficiency, requiring no special calibration on start-up; 7. Be approved
for 0˝ clearance to combustibles.
The control shall be an integrated solid-state temperature and ignition control device with integral diagnostics, graphic user interface, fault history display, and shall have digital temperature readout.
1. All models are design certified by Underwriters Laboratories (UL), Inc., according to ANSI Z21.10.3 - CSA 4.3 standards governing storage type water heaters; 2. Meet the thermal efficiency and standby loss
requirements of the U. S. Department of Energy and current edition ASHRAE/IESNA 90.1. Complies with SCAQMD Rule 1146.2 and other air quality management districts with similar requirements for low NOx emissions.
120K-250K BTU Input:
For Standard Power Venting: Water heater(s) shall be suitable for power venting using a (3˝ or 4˝ ) _______ diameter PVC pipe for a total distance of (50 ft or 120 ft.) ______ equivalent feet of vent piping.
For Power Direct Venting: Water heater(s) shall be suitable for power direct venting using a (3˝ or 4˝ ) _______ diameter PVC pipe for a total distance of (50 ft or 120 ft.) ______ equivalent feet of vent piping and
(50 ft. or 120 ft.)______ equivalent feet of intake air piping.
300K - 500K BTU Input:
For Standard Power Venting: Water heater(s) shall be suitable for standard power venting using a (4˝ or 6˝ )______ diameter PVC pipe for a total distance of (70 ft. or 120 ft.)_____ equivalent feet of vent piping.
For Power Direct Venting: Water heater(s) shall be suitable for power direct venting using a (4˝ or 6˝ ) _______ diameter PVC pipe for a total distance of (70 ft or 120 ft.) ______ equivalent feet of vent piping and
(50 ft. or 120 ft.)______ equivalent feet of intake air piping.
Operation of the water heater(s) in a closed system where thermal expansion has not been compensated for (with a properly sized thermal expansion tank) will void the warranty.
Water heater should incorporate the iCOMM
system for remote monitoring, leak detection and fault alert.
MODEL U.S. GALLONS LITERS
BTH-120(A) 60 227
BTH-150(A) 100 379
BTH-199(A) 100 379
BTH-250(A) 100 379
BTH-300(A) 119 450.96
BTH-400(A) 119 450.96
BTH-500(A) 119 450.96
MODEL NATURAL GAS PROPANE GAS
BTH-120(A) 3/4˝ NPT 3/4˝ NPT
BTH-150(A) 3/4˝ NPT 3/4˝ NPT
BTH-199(A) 3/4˝ NPT 3/4˝ NPT
BTH-250(A) 3/4˝ NPT 3/4˝ NPT
BTH-300(A) 1 1/2˝ NPT 1 1/2˝ NPT
BTH-400(A) 1 1/2˝ NPT 1 1/2˝ NPT
BTH-500(A) 1 1/2˝ NPT 1 1/2˝ NPT
GAS LINE CONNECTION SIZE
STORAGE CAPACITIES
RECOVERY CAPACITY