Brochure
37
XB Model Boilers
Precise temperature control and
accurate load matching results in
smooth system operation
BOILERS
Direct Vent Flexibility
Direct vent up to 100 equivalent feet of pipe
Sidewall or vertical
Lower installation cost with approved CPVC/PVC venting material – uses CPVC
for first 10 feet and PVC thereafter.
Approved for use with UL approved AL29-4C
®
stainless steel venting materials
Factory Start-Up Included
Required for activating warranty and assuring maximum operating
performance. Contact your local sales representative or Authorized
Start-Up Agent to arrange a FREE certified start-up.
Category IV Listed
Approved for use with CPVC/PVC venting material – uses CPVC for
first 10 feet then PVC thereafter or a UL approved AL 29-4C Stainless
Steel venting material
Professional Start-Up Service Included
Assures optimum performance for each installation
Meets the Thermal Efficiency Requirements of the U.S.
Department of Energy and Current Edition ASHRAE/IESNA 90.1
10-Year Heat
Exchanger
Warranty
For complete information, consult written warranty or contact A. O. Smith
Other XP Boiler Features:
93% thermal efficiency (AHRI certified)
Certified to ANSI Z21.13-CSA 4.9
Honeywell sola control with color touch screen LCD display
· Inlet/outlet and remote loop temperature display
· Onboard modbus communications
· Logs faults, run time, cycles
· Redundant flow and low water protection - factory-installed LWCO and flow switch(s)
· Multi-burner sequencing models 2 million btuh and up have 4 burners; models 1.7 million btuh and down have 2 burners
· Redundant ignition controls – should one burner fail remaining burners continue to heat
· Alarm buzzer
· Outdoor temperature sensor included
20:1 turndown models 2 million btuh
and up, 10:1 turndown models 1.7
million btuh and down
Horizontal and vertical direct and
sidewall vent options up to 100
equivalent feet of piping
Approved for CPVC/PVC plastic vent
materials
Meets ASME CSD-1/GE gap codes –
factory standard
Direct spark ignition
Factory-installed electrical disconnect
316L Stainless steel heat exchanger
ASME 160# working pressure
ASME rated pressure relief valve – 50 PSI
XP Boiler Options:
Factory-mounted secondary pump
(recommended for primary/secondary
piping systems)
Condensate neutralization kit
Vent termination kits
Skid mounted systems
XXBB MMOODDEELLSS -- FFLLOOWW,, HHEEAADD AANNDD TTEEMMPPEERRAATTUURREE RRIISSEE
Models
Input
(Btu/hr)
Output
(Btu/hr)
Water
Flow
Temperature Rise - ΔT °F
Flow Rate
20 30 40 Maximum Minimum
XB-1000 920,000 855,600
GPM 86 57 43 86 43
LPM 324 216 162 324 162
ΔP FT
26 12 7 26 7
ΔP M
7.9 3.7 2.1 8 2.1
XB-1300 1,300,000 1,209,000
GPM 121 81 60 121 60
LPM 458 305 229 458 229
ΔP FT
32.5 15 8 32.5 8
ΔP M
9.9 4.6 2.4 9.9 2.4
XB-1700 1,700,000 1,581,000
GPM 158 105 79 158 79
LPM 598 399 299 598 299
ΔP FT
35 14 8 35 8
ΔP M
10.7 4.3 2.4 10.7 2.4
XB-2000 1,999,900 1,859,907
GPM 186 124 93 186 93
LPM 704 469 352 704 352
ΔP FT
26 12 7 26 7
ΔP M
7.9 3.7 2.1 7.9 2.1
XB-2600 2,600,000 2,418,000
GPM 242 161 121 242 121
LPM 915 610 458 915 458
ΔP FT
32.5 15 8 33 8
ΔP M
9.9 4.6 2.4 9.9 2.4
XB-3400 3,400,000 3,162,000
GPM 316 211 158 316 158
LPM 1197 798 598 1197 598
ΔP FT
35 14 8 35 8
ΔP M
10.7 4.3 2.4 11 2.4
AOSCA80000 R Oct 2011 Com Catalog:108078_ResidentialFul#7A635.qxd 10/28/11 5:52 PM Page 37