User Guide
Table Of Contents
- Safe Installation, Use and Service
- APPROVALS
- General safety INFORMATION
- Introduction
- Installation Considerations
- Installation requirements
- Gas Supply Systems
- Gas Pressure Requirements
- Supply Gas Regulator
- Mixing Valves
- Water Piping
- Temperature-Pressure Relief Valve
- Filling the Water Heater
- Air Requirements
- Unconfined Space
- Confined Space
- Fresh Air Openings For Confined Spaces
- Outdoor Air Through Two Openings
- Outdoor Air Through One Opening
- Outdoor Air Through Two Horizontal Ducts
- Outdoor Air Through Two Vertical Ducts
- Air From Other Indoor Spaces
- Venting
- Gas Piping
- Sediment Traps
- Temperature Regulation
- For Your Information
- Periodic Maintenance
- Venting System Inspection
- Burner Inspection
- Burner Cleaning
- Air Shutter Adjustment
- Housekeeping
- Anode Rod Inspection
- Temperature-Pressure Relief Valve Test
- Periodic Removal of Lime Deposits From Tank Type Commercial Water Heaters
- Deliming Solvents
- Tank Cleanout Procedure
- Deliming Using Flo-Jug Method
- Draining and Flushing
- Service
- Leakage Test Points
- Water Piping Diagrams
- Commercial Water Heater Limited Warranty
9
HIGH ALTITUDE
Water heaters covered in this manual have been tested
and approved for installation at elevations up to 7,700
feet (2,347 m) above sea level. For installation above
7,700 feet (2,347 m), the water heater’s Btu input should
be reduced at the rate of 4 percent for each 1,000 feet
(305 m) above sea level which requires replacement of
the burner orice in accordance with the National Fuel
Gas Code ANSI Z223.1/NFPA 54 or the Natural Gas and
Propane Installation Code CAN/CSA B149.1. Contact
your local gas supplier for further information.
Failure to replace the standard orice with the proper
high altitude orice when installed at elevations above
7,700 feet (2,347 m) could result in improper and
inefcient operation of the water heater, producing
carbon monoxide gas in excess of the safe limits. This
could result in serious injury or death. Contact your
local gas supplier for any specic changes that may be
required in your area.
ADJUSTING AIR SHUTTER FOR HIGHER ALTI-
TUDES
The air shutter is preset with the air shutter in the open
position and for most applications changing the air
shutter is not required.
FIGURE 2. AIR SHUTTER OPEN
A correctly set burner should have a stable quiet ame.
The ame will be blue with a well dened blue inner
ame, Some yellow tipping is normal with LP gas. See
Figure 3.
FIGURE 3. NORMAL FLAMES
If ames are seen to lift from the burner ports, gradually
close the air shutter until a stable ame is achieved. See
Figure 4.
FIGURE 4. FLAME LIFTING
See Figure 5 for the appearance of the half-closed and
full-closed air shutter. Normally, this ame lifting occurs
only at altitudes above 5,400 feet.
FIGURE 5. HALF-CLOSED AND CLOSED AIR SHUTTER
If the air shutter is closed too far, the ame will look hazy
and not have dened cones. See the example in Figure
6 (page 10). In this case, the air shutter will need to be
opened. See Figure 2.