User Guide
Table Of Contents
- Safe Installation, Use and Service
- APPROVALS
- General safety INFORMATION
- Introduction
- Installation Considerations
- Installation requirements
- Gas Supply Systems
- Gas Pressure Requirements
- Supply Gas Regulator
- Mixing Valves
- Water Piping
- Temperature-Pressure Relief Valve
- Filling the Water Heater
- Air Requirements
- Unconfined Space
- Confined Space
- Fresh Air Openings For Confined Spaces
- Outdoor Air Through Two Openings
- Outdoor Air Through One Opening
- Outdoor Air Through Two Horizontal Ducts
- Outdoor Air Through Two Vertical Ducts
- Air From Other Indoor Spaces
- Venting
- Gas Piping
- Sediment Traps
- Temperature Regulation
- For Your Information
- Periodic Maintenance
- Venting System Inspection
- Burner Inspection
- Burner Cleaning
- Air Shutter Adjustment
- Housekeeping
- Anode Rod Inspection
- Temperature-Pressure Relief Valve Test
- Periodic Removal of Lime Deposits From Tank Type Commercial Water Heaters
- Deliming Solvents
- Tank Cleanout Procedure
- Deliming Using Flo-Jug Method
- Draining and Flushing
- Service
- Leakage Test Points
- Water Piping Diagrams
- Commercial Water Heater Limited Warranty
28
AIR SHUTTER ADJUSTMENT
If the installation is at a high elevation and the burner
ame exhibits ame lifting and/or noise, do the following:
1. Use a screw driver to loosen the air shutter screw.
2. Adjust the air shutter by rotating the shutter. Counter
clockwise to close and Clockwise to open.
a. Close air shutter - to prevent noisy ames that are
lifting from the burner ports.
b. Open air shutter – to reduce yellow tipping of the
ame. (A small number of yellow tips can be normal
to LP gases.)
3. Tighten the air shutter screw to secure the air shutter.
See Adjusting Air Shutter for Higher Altitudes (page
9).
HOUSEKEEPING
Fire and Explosion Hazard
Do not obstruct combustion air
openings at the bottom of the
water heater.
Do not use or store flammable vapor
products such as gasoline, solvents
or adhesives in the same room or area
near water heater or other appliance.
Can cause serious injury or death.
Vacuum around base of water heater for dust, dirt, and
lint on a regular basis.
INSTALLED IN SUITABLE AREA: To insure sufcient
ventilation and combustion air supply, proper clearances
from the water heater must be maintained. See Facts to
Consider About the Location (page 7). Combustible
materials such as clothing, cleaning materials, or
ammable liquids, etc. must not be placed against or
adjacent to the water heater which can cause a re.
ANODE ROD INSPECTION
Property Damage Hazard
•
Avoid water heater damage.
•
Inspection and replacement of anode rod required.
CAUTION
The anode rod is used to protect the tank from corrosion.
Most hot water tanks are equipped with an anode rod.
The submerged rod sacrices itself to protect the tank.
Instead of corroding the tank, water ions attack and eat
away the anode rod. This does not affect water’s taste
or color. The rod must be maintained to keep the tank in
operating condition.
Anode deterioration depends on water conductivity, not
necessarily water condition. A corroded or pitted anode
rod indicates high water conductivity and should be
checked and/or replaced more often than an anode rod
that appears to be intact. Replacement of a depleted
anode rod can extend the life of your water heater.
Inspection should be conducted by a qualied service
agency, and at a minimum should be checked annually
after the warranty period.
Articially softened water is exceedingly corrosive
because the process substitutes sodium ions for
magnesium and calcium ions.
The use of a water softener may decrease the life of the
water heater tank.
The anode rod should be inspected after a maximum of
three years and annually thereafter until the condition of
the anode rod dictates its replacement.
NOTE: Articially softened water requires the anode rod
to be inspected annually.
TEMPERATURE-PRESSURE RELIEF VALVE TEST
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.
It is recommended that the temperature-pressure relief
valve should be checked to ensure that it is in operating
condition every 6 months.
When checking the temperature-pressure relief valve