User Guide
Table Of Contents
- Safe Installation, Use and Service
- APPROVALS
- General safety INFORMATION
- Introduction
- Installation Considerations
- Installation requirements
- Gas Supply Systems
- Gas Pressure Requirements
- Supply Gas Regulator
- Mixing Valves
- Water Piping
- Temperature-Pressure Relief Valve
- Filling the Water Heater
- Air Requirements
- Unconfined Space
- Confined Space
- Fresh Air Openings For Confined Spaces
- Outdoor Air Through Two Openings
- Outdoor Air Through One Opening
- Outdoor Air Through Two Horizontal Ducts
- Outdoor Air Through Two Vertical Ducts
- Air From Other Indoor Spaces
- Venting
- Gas Piping
- Sediment Traps
- Temperature Regulation
- For Your Information
- Periodic Maintenance
- Venting System Inspection
- Burner Inspection
- Burner Cleaning
- Air Shutter Adjustment
- Housekeeping
- Anode Rod Inspection
- Temperature-Pressure Relief Valve Test
- Periodic Removal of Lime Deposits From Tank Type Commercial Water Heaters
- Deliming Solvents
- Tank Cleanout Procedure
- Deliming Using Flo-Jug Method
- Draining and Flushing
- Service
- Leakage Test Points
- Water Piping Diagrams
- Commercial Water Heater Limited Warranty
19
The conned space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of
the top and one commencing within 12 inches (300 mm)
of the bottom of the enclosure. See Figure 17.
Each opening shall communicate directly with an
additional room(s) of sufcient volume so that the
combined volume of all spaces meets the criteria for an
unconned space.
Each opening shall have a minimum free area of 1
square inch per 1,000 Btu/hr (2200 mm
2
per kW) of the
aggregate input rating of all appliances installed in the
enclosure. Each opening shall not be less than 100
square inches (645 cm
2
).
VENTING
Water heaters covered by these instructions are Category
I, Natural Draft appliances.
If the water heater is being installed as a replacement
for an existing heater in pre-existing venting, a thorough
inspection of existing venting system must be performed
prior to any installation work.
VENT DAMPERS - Any vent damper, whether it is
operated thermally or otherwise must be removed if its
use inhibits proper drafting of the water heater.
Thermally Operated Vent Dampers: this gas-red water
heater has a thermal efciency at or above 80% which
may produce a relatively low ue gas temperature.
Such temperatures may not be high enough to properly
open thermally operated vent dampers. This would
cause spillage of the ue gases and may cause carbon
monoxide poisoning. Vent dampers must bear evidence
of certication as complying with the current edition of
the American National Standard ANSI Z21.66 CGA 6.14
(covering electrically and mechanically actuated vent
dampers). Before installation of any vent damper, consult
the local gas utility for further information.
To insure proper venting of this gas-red water heater,
the correct vent pipe diameter must be utilized. Any
additions or deletions of other gas appliances on a
common vent with this water heater may adversely affect
the operation of the water heater. Consult your gas
supplier if any such changes are planned.
For proper venting in certain installations, a larger
diameter vent pipe may be necessary. Consult your gas
supplier to aid you in determining the proper venting
for your water heater from the vent tables in the current
edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54
or the Natural Gas and Propane Installation Code CAN\CSA
B 149.1.
Periodically check the venting system for signs of
obstruction or deterioration and replace if needed.
The combustion and ventilation air ow must not be
obstructed.
The water heater with draft hood installed must be
connected to a chimney or listed vent pipe system,
which terminates to the outdoors. Never operate the
water heater unless it is vented to the outdoors and has
adequate air supply to avoid risks of improper operation,
explosion or asphyxiation.
• For proper draft hood attachment, the draft hood legs
may be angled slightly inward.
• Place the draft hood legs in the receiving holes on the
top of the water heater. The legs will snap in the holes
to give a tight t. Secure draft hood with the supplied
brackets.
• Place the vent pipe over the draft hood. With the vent
pipe in position, drill a small hole through both the
vent pipe and draft hood. Secure them together with a
sheet metal screw. See Figure 18 (page 20).
Obstructed or deteriorated vent systems may present
serious health risk or asphyxiation.