CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements
or such conditions as high line pressure, among others,
have installed devices such as pressure-reducing valves,
check valves, and back fl ow preventers. Devices such
as these cause the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a
closed system, the volume of water will increase. As the
volume of water increases, there will be a corresponding
increase in water pressure due to thermal expansion.
Thermal expansion can cause premature tank failure
(leakage). This type of failure is not covered under the
limited warranty. Thermal expansion can also cause
intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure
build up. The temperature-pressure relief valve is not
intended for the constant relief of thermal expansion. This
condition is not covered under the limited warranty.
METAL
DRAIN
PAN
FLOOR
DRAIN
HOT-WATER
OUTLET
COLD-
WATER
INLET
UNION UNION
3/4” SWEAT
FITTING
3/4” SWEAT
FITTING
TEMPERATURE-
PRESSURE
RELIEF VALVE
DISCHARGE PIPE
(DO NOT CAP
OR PLUG)
6 in.
MAX. AIR
GAP
DRAIN
VALVE
SHUT-OFF VALVE
SOME
COMPONENTS
NOT SHOWN
FOR CLARITY.
Figure 15
A properly-sized thermal expansion tank should be
installed on all closed systems to control the harmful
effects of thermal expansion. Contact a plumbing service
agency or your retail supplier regarding the installation of
a thermal expansion tank.
Note: To protect against untimely corrosion of hot and cold
water fi ttings, it is recommended that di-electric unions or
couplings be installed on this water heater when connected
to copper pipe.
• Avoid water heater damage.
• Install thermal expansion tank if necessary.
• Do not apply heat to cold water inlet.
• Contact qualified installer or service agency.
Property Damage Hazard
CAUTION
Figure 15 shows typical attachment of water piping to the
water heater. The water heater is equipped with 3/4” NPT
water connections.
Note: If using copper tubing, solder tubing to an
adapter before attaching the adapter to the water heater
connections. Do not solder the water lines directly to the
water heater connections - it will harm the dip tube and
heat traps and damage the tank.
TEMPERATURE-PRESSURE RELIEF VALVE
• Temperature-pressure relief
valve must comply with ANSI
Z21.22-CSA4.4 and ASME
code.
• Properly sized temperature-
pressure relief valve must be
installed in opening provided.
• Do not plug, block, or cap the
discharge line.
• Failure to follow this warning
can result in excessive tank
pressure, serious injury or
death.
Explosion Hazard
WARNING
This water heater is provided with a properly rated/sized
and certifi ed combination Temperature-Pressure Relief
Valve (T&P valve) by the manufacturer. The valve is
certifi ed by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed
equipment of materials as meeting the requirements for
Relief Valves for Hot Water Supply Systems, ANSI
Z21.22-CSA 4.4, and the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements
of local codes, but not less than a combination temperature-
pressure relief valve rated/sized and certifi ed as indicated
in the above paragraph. The new valve must be marked
with a maximum set pressure not to exceed the marked
hydrostatic working pressure of the water heater (150 psi)
and a discharge capacity not less than the water heater
Btu/hr input rate as shown on the water heater’s model
rating plate.