User Guide

10
GAS SUPPLY SYSTEMS
Low pressure building gas supply systems are dened as those
systemsthatcannotunderanycircumstancesexceed14”W.C.
(1/2PSIGauge).Thesesystemsdonotrequirepressureregulation.
Measurementsshouldbetakentoinsurethatgaspressuresarestable
andfallwithintherequirementsstatedonthewaterheaterratingplate.
readingsshould be takenwith all gas burning equipment off (static
pressure)andwithallgasburningequipmentrunningatmaximumrate
(dynamicpressure).Thegassupplypressuremustbestablewithin1.5”
W.C.fromstatictodynamicpressuretoprovidegoodperformance.
Pressuredropsthatexceed1.5”W.C.maycauseroughstarting,noisy
combustionornuisanceoutages.Increasesorspikesinstaticpressure
duringoffcyclesmaycausefailuretoigniteorinseverecasesdamage
toappliancegasvalves.Ifyourlowpressuresystemdoesnotmeet
theserequirements,theinstallerisresponsibleforthecorrections.
HighPressurebuildingsupplysystemsusepressuresthatexceed
14” W.C. (1/2 PSI Gauge).These systems must use eld supplied
regulatorstolowerthegaspressuretolessthan14”W.C.(1/2PSI
Gauge).Appliancesrequiregasregulatorsthatareproperlysizedforthe
waterheaterinputanddelivertheratingplatespeciedpressures.Gas
supplysystemswherepressureexceeds5PSIoftenrequiremultiple
regulatorstoachievedesiredpressures.Systemsinexcessof5PSI
buildingpressureshouldbedesignedbygasdeliveryprofessionals
forbestperformance.Waterheatersconnectedtogassupplysystems
thatexceed14”W.C.(1/2PSIGauge)atanytimemustbeequipped
withagassupplyregulator.
GAS PRESSURE REQUIREMENTS
BL-100naturalgasmodelrequiresaminimumgassupplypressureof
5”w.c.(1.25kPa);BL-80naturalgasmodelrequiresaminimumgas
supplypressureof6”w.c.(1.49kPa).Theminimumsupplypressure
is measured while gas is owing (dynamic pressure). The supply
pressure(dynamic)shouldneverfallbelowthespeciedminimum
supplypressure.Thesupplypressureshouldbemeasuredwithallgas
redappliancesconnectedtothecommonmainringatfullcapacity.If
thesupplypressuredropsmorethan1.5”W.C.(0.37kPa)asgasbegins
toowtothewaterheaterthenthesupplygassystemincludingthe
gaslineand/orthegasregulatormayberestrictedorundersized.See
SupplyGasregulatorsectionandGasPipingsectionofthismanual.
Thegasvalveonallmodelshasamaximumgassupplypressurelimit
of14”W.C.(3.48kPa)Themaximumsupplypressureismeasured
whilegasisnotowing(staticpressure).
SUPPLY GAS REGULATOR
Themaximumallowablegassupplypressureforthiswaterheater
is14.0inchesW.C.(3.48kPa).Installapositivelock-upgaspressure
regulatorinthegassupplylineifinletgaspressurecanexceed14.0
inchesW.C.(3.48kPa)atany time. regulators mustbesized/used
accordingtomanufacturer’sspecications.
Ifapositivelock-upregulatorisrequiredfollowtheseinstructions:
1. Positivelock-upgaspressureregulatorsmustberatedatorabove
theinputBtu/hrratingofthewaterheatertheysupply.
2. Positivelock-upgaspressureregulator(s)shouldbeinstalledno
closerthan3feet(1meter)andnofartherthan8feet(2.4meters)
ofequivalentlengthfromthewaterheater’sinletgasconnection.
3. Afterinstallingthepositivelock-upgaspressureregulator(s)aninitial
nominalsupplypressuresettingof7.0”W.C.whilethewaterheater
isoperatingisrecommendedandwillgenerallyprovidegood
waterheateroperation.Someadditionaladjustmentmayberequired
latertomaintainasteadygassupplypressure.
4. When installing multiple water heaters in the same gas supply
system it is recommended that individual positive lock-up gas
pressureregulatorsbeinstalledateachunit.
MIXING VALVES
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the physically
or mentally disabled are at highest risk
for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as
mixing valves must be installed when
required by codes and to ensure safe
temperatures at fixtures.
Waterheatedtoatemperaturewhichwillsatisfyclotheswashing,dish
washing,andothersanitizingneedscanscaldandcausepermanent
injuryuponcontact.Shortrepeatedheatingcyclescausedbysmall
hotwaterusescancausetemperaturesatthepointofusetoexceed
thewaterheater’stemperaturesettingbyupto20°F(11°C).
Somepeoplearemorelikelytobepermanentlyinjuredbyhotwater
than others. These include the elderly, children, the inrm and the
physically/mentally disabled.Table 2 shows the approximate time-
to-burnrelationshipfornormaladultskin.Ifanyoneusinghotwater
provided by the water heater being installed ts into one of these
groupsorifthereisalocalcodeorstatelawrequiringacertainwater
temperatureatthepointofuse,thenspecialprecautionsmustbetaken.
In addition to using the lowest possible temperature setting that
satisesdemandoftheapplicationaMixingValveshouldbeinstalled
atthewaterheaterorathotwatertapstofurtherreducesystemwater
temperature.SeeFigure6.
Mixing valves are available at plumbing supply stores. Consult
a Qualied Installer or Service Technician. Follow mixing valve
manufacturer’sinstructionsforinstallationofthevalves.
TABLE 2.
Water
Temperature°F
Timefor
1stDegreeBurn
(LessSevereBurns)
TimeforPermanentBurns
2nd&3rdDegree
(MostSevereBurns)
110
(normalshowertemp.)
116 (painthreshold)
116 35minutes 45minutes
122 1minute 5minutes
131 5seconds 25seconds
140 2seconds 5seconds
149 1second 2seconds
154 instantaneous 1second
(U.S.GovernmentMemorandum,C.P.S.C.,PeterL.Armstrong,Sept.15,1978)
HOT WATER
OUTLET
TO TANK
INLET
CHECK
VALVE
MIXING
VALVE
COLD
WATER
INLET
TEMPERED WATER
OUTLET
12” TO 15”
(30-38 cm)
CHECK
VALVE
FIGURE 6.
INSTALLATION REQUIREMENTS