Datasheet
For industrial environments
EtherCAT Features
The following features are not supported:
- Acyclic data transfer using Service Data Objects (SDOs) (only cyclic data transfer using PDOs supported)
- Ethernet over EtherCAT (EoE)
- Servo Profile over EtherCAT (SoE)
- Redundancy with ring topology
- Import EtherCAT Slave Information (ESI) files (EtherCAT SubDevices need to be scanned)
- Select SubDevice data to be mapped towards the control system (default data is always mapped)
PROFINET FEATURES
ANYBUS' SECOND-GENERATION GATEWAYS OFFER WORLD-LEADING USABILITY THANKS TO THE INTUITIVE GRAPHICAL
USER INTERFACE (GUI).
The User Interface enables you to:
Robust, compact housing.
Industrial components are CE and UL tested and certified.
Wide temperature range, -25°C to 70°C.
Top-hat rail mounting for installation close to the connected devices, reducing wiring effort.
EtherCAT MainDevice
Transfer up to 1500 to and from EtherCAT (3000 bytes in total)
1 ms cycle time (configurable)
Up to 24 EtherCAT SubordinateDevices (slaves)
CANOpen Over EtherCAT (CoE)
Cyclic data transfer using Process Data Objects (PDOs)
Scan for EtherCAT SubordinateDevices (ESI files are not supported)
Live list - Monitor EtherCAT SubordinateDevice status from control system
Data exchange control – Enable/disable EtherCAT SubordinateDevice from control system
Clone configuration – scan an EtherCAT network once and re-use the configuration for identical systems
PROFINET IO-Device (slave)
Transfer up to 1 024 bytes to and from PROFINET (2048 bytes total)
1 ms minimum cycle time
Conformance class B, Real-Time (RT)
High robustness against network load, Netload Class III
Dual RJ45 Ethernet ports with 10/100 Mbit full duplex
Daisy chaining with integrated switch
Change the configurations without installing additional software
Use drag and drop functionality to configure the gateway