Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
7.7.3. Congure Frame Fields Sengs
Procedure
Figure 40. Frame Fields Sengs
1. In the Transacon templates list, select a transacon template to congure.
2. In the Transacon template sengs select a Field to congure.
The Field sidebar opens, on the right side of the screen.
3. Congure the Field sengs.
Node address
• Frame eld represenng the Node address of the node. A constant byte that holds a copy of the nodes
address when the transacon is used by a node.
• When the transacon template is used by a node, the Node address eld will automacally be replaced with
the actual node address of the node.
Constant
• Name: You can name the Frame Field to make it easier to idenfy.
• Type: Specify the number of bytes in the frame.
Select Byte (1 byte) (Default), Word (2 bytes), Double word (4 bytes), Array of bytes or String.
• Endianess: Select Big-endian (Default) or Lile-endian.
• Fixed eld*: Select Yes, set here (Default) or No, set when used.
• Length: Valid for Array of bytes. Enter a byte oset value between 0 and 32 byte.
Default value is 1 byte.
Enter a Value for each Byte (0–31).
• Value: The value of the Constant in the frame.
Enter a value between 0 (Default) and 255.
• Min value: Specify the minimum value that can be set when the template is used.
• Max value: Specify the maximum value that can be set when the template is used.
• Default value: Default value set when the template is used.
Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial Build Transacon Template
Page 60 of 134 SCM-1202-177 1.2