Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
5.5.2. Set a Node Address with Rotary Switches
About the Rotary Switch Sengs
To set a node address for the PROFIBUS server, use the rotary switches located on the top front of the
Communicator .
TIP
Use Windows Calculator (or similar applicaon) to convert between hexadecimal (hex) and
decimal (dec).
• The default node address seng is 000.
• When the node address seng is 000, you can se the node address via the Communicator built-in web
interface.
See PROFIBUS Address Sengs (page 77).
• The node address values are set in hexadecimal (hex).
• Minimum value is 00.
• Supports PROFIBUS node addresses 0-126 Dec (0-7E Hex).
• Each node address may only occur once in the network.
• The node address is read from the center rotary switch x16 to the front rotary switch x1.
• The rear rotary switch is not used, ensure that it is set to 0.
Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial Rotary Switch Sengs