Instructions
Basic Network Configuration 38
Doc: HMSI-27-314, Rev. 3.10Anybus Communicator EtherNet/IP / Modbus-TCP User Manual
6.2 Ethernet Configuration File (‘ethcfg.cfg’)
6.2.1 General
To exist on the network, the Anybus Communicator needs a valid TCP/IP configuration. These settings 
are stored in the system file ‘\ethcfg.cfg’. Note that if TCP/IP settings are enabled in Anybus Configu-
ration Manager, then the IP address, gateway and subnet settings in ethcfg.cfg will be overwritten every 
time the module is restarted. All other settings are unaffected.
The settings in this file may also be affected by...
• EtherNet/IP (See “EtherNet/IP” on page 37).
• HICP (See “Anybus IPconfig (HICP)” on page 41)
• SSI (See “Server Side Include (SSI)” on page 45)
See also...
•  “FTP Server” on page 30
•  “Fieldbus Settings” on page 64
File Format:
[IP address]
xxx.xxx.xxx.xxx
[Subnet mask]
xxx.xxx.xxx.xxx
[Gateway address}
xxx.xxx.xxx.xxx
[DHCP/BOOTP]
ON or OFF
[SMTP address]
xxx.xxx.xxx.xxx
[SMTP username]
username
[SMTP password]
password
[DNS1 address]
xxx.xxx.xxx.xxx
[DNS2 address]
xxx.xxx.xxx.xxx
[Domain name]
domain
[Host name]
anybus
[HICP password]
password
• IP address
• Subnet mask
• Gateway address
• DHCP/BootP
ON - Enabled
OFF - Disabled
• SMTP server/login settings
Username and Password is only necessary if required by the 
server.
• Primary and Secondary DNS
Needed to be able to resolve host names
• Default domain name for not fully qualified host names
•Host name
•HICP password