D. Troubleshooting
Problem Solution
Problem during configuration Upload / Download.
The Config Line “LED” turns red in ACM.
Serial communication failed. Try again
The serial port seems to be available, but it is not possible
to connect to the gateway
The serial port may be in use by another application.
Exit ACM and close all other applications including the
ones in the system tray.
Try again
Select another serial port
Try again
Poor performance Right click “sub-network” in the Navigation window and
select “sub-network Status” to see status / diagnostic
information about the sub-network.
If the gateway reports very many retransmissions, check
your cabling and/or try a lower baud rate setting for the
sub-network (if possible).
Is the Subnet Monitor in ACM active?
The sub-network monitor has a negative influence on the
overall performance of the gateway, and should only be
used when necessary.
Is the Node Monitor in ACM active?
The node monitor has a negative influence on the overall
performance of the gateway, and should only be used
when necessary.
No sub-network functionality Use the “Data logger”-functionality to record the serial
data communication on the sub-network.
If no data is being transmitted, check the configuration in
ACM.
If no data is received, check the sub-network cables. Also
verify that the transmitted data is correct.