Additional installation and operating instructions
Max Ambient Temperature: 55 °C (for Hazloc environments)
Field wiring terminal markings (wire type (Cu only, 14–30 AWG)).
Use 60/75 or 75 °C copper (Cu) wire only.
Terminal tightening torque must be 5–7 lb-in (0.5–0.8 Nm).
Use in overvoltage category 1 pollution degree 2 environment.
Installed in an enclosure considered representative of the intended use.
Secondary circuit intended to be supplied from an isolating source and protected by overcurrent
protective devices installed in the field sized per the following:
Galvanic isolation on sub-network interface
EN 60950-1 (2001)
Pollution Degree 2
Material Group IIIb
250 V
RMS
or 250 VDC working voltage
500 V secondary circuit transient rating
CIP Product Compliance
Control circuit wire size Maximum protective device rating
AWG mm² Amperes
22 0.32 3
20 0.52 5
18 0.82 7
16 1.3 10
14 2.1 20
12 3.3 25