Instructions
About the Anybus Communicator for EtherNet/IP 13
Doc: HMSI-27-314, Rev. 3.10Anybus Communicator EtherNet/IP / Modbus-TCP User Manual
1.2 Status LEDs
# State Status
1 - Module Status
(EtherNet/IP only)
Off No power
Green Controlled by a scanner in run state
Green, flashing Not configured, or scanner in idle state
Red Major fault (unrecoverable)
Red, flashing Minor fault (recoverable)
Alternating Red/Green Self-test
2 - Network Status
(EtherNet/IP only)
Off No IP address (or no power)
Green Online, EtherNet/IP connection(s) established
Green, flashing Online, no EtherNet/IP connections established
Red Duplicate IP address detected, fatal error
Red, flashing One or more connections timed out
Alternating Red/Green Self-test
3 - Link Off No link (or no power)
Green Connected to an ethernet network
4 - Activity Off No ethernet activity (or no power)
Green Receiving or transmitting ethernet packet
5 - Subnet Status
a
a. This LED shows green when all transactions have been active at least once. This includes
any transactions using “change of state” or “change of state on trigger”. If a timeout occurs
on a transaction, this LED will show red.
Off (no power)
Green, flashing Running correctly, but one or more transaction
error(s) have occurred
Green Running
Red Transaction error/timeout or subnet stopped
6 - Device Status Off (no power)
Alternating Red/Green Invalid or missing configuration
Green Initializing
Green, flashing Running
Red
Bootloader mode
b
b. The gateway is in bootloader mode, and firmware must be restored in order for it to work
properly. Start up the Anybus Configuration Manager and connect to the Anybus Commu-
nicator. Select Tools/Options/Module. Click Factory Restore to restore firmware. See
“Tools” on page 61.
Red, flashing If the Device Status LED is flashing in a sequence
starting with one or more red flashes, please note
the sequence pattern and contact HMS support.
1
3
5
2
4
6