Instructions

CIP Object Implementation 113
Doc: HMSI-27-314, Rev. 3.10Anybus Communicator EtherNet/IP / Modbus-TCP User Manual
22.7 Parameter Data Output Mapping Object, Class B1h
22.7.1 General Information
Object Description
This object can be used to access output data acyclically, and is set up dynamically based on the Param-
eter Data Mailbox initialization (see “Parameter Data Initialization (Explicit Data)” on page 119).
See also...
“EtherNet/IP” on page 23
“Fieldbus Settings” on page 64
“Parameter Data Input Mapping Object, Class B0h” on page 112
“Parameter Data Initialization (Explicit Data)” on page 119
Supported Services
Class services: Get Attribute All
Instance services: Get Attribute Single
Set Attribute Single
22.7.2 Class Attributes
22.7.3 Instance Attributes, Instance 01h
Each attribute corresponds to a block of output data. Note that the size and location of each block must
be specified using the Anybus Configuration Manager.
For more information, see “Parameter Data Initialization (Explicit Data)” on page 119
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
# Access Name Type Description
01h Get/Set Data Array of USINT Mapped block of Output Data
02h Get/Set Data Array of USINT Mapped block of Output Data
01h Get/Set Data Array of USINT Mapped block of Output Data
02h Get/Set Data Array of USINT Mapped block of Output Data
01h Get/Set Data Array of USINT Mapped block of Output Data
02h Get/Set Data Array of USINT Mapped block of Output Data
... ... ... ... ...
32h Get/Set Data Array of USINT Mapped block of Output Data