Instructions
Anybus Communicator Installation Sheet
www.anybus.com
UL Certifi cation
Control-circuit Wire Size Maximum Protective Device 
Rating
AWG (mm
2
) Amperes
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
14 (2.1) 20
12 (3.3) 25
Further information and documents about this product can be 
found at the product pages on www.anybus.com.
IND: CONT. EQ.
FOR HAZ LOC.
CL I, DIV 2
GP A,B,C,D
TEMP
CODE
 E203225
Warnings
•  WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 
ANY COMPONENTS MAY IMPAIR SUITABILITY FOR 
CLASS I, DIVISION 2.
•  WARNING - EXPLOSION HAZARD - WHEN IN 
HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE 
REPLACING OR WIRING MODULES.
•  WARNING - EXPLOSION HAZARD - DO NOT 
DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN 
SWITCHED OFF OR THE AREA IS KNOWN TO BE 
NONHAZARDOUS.
Max Ambient Temperature: 55°C (for Hazloc environments)
Field wiring terminal markings (wire type (Cu only, 14-30 AWG)).
Use 60/75 or 75°C copper (Cu) wire only.
Terminal tightening torque must be between 5-7 lb-in (0.5 - 0.8 
Nm).
Use in overvoltage category 1 pollution degree 2 environment.
Installed in an enclosure considered representative of the in-
tended use.
Secondary circuit intended to be supplied from an isolating 
source and protected by overcurrent protective devices installed 
in the fi eld sized per the following:
This product is in accordance with the EMC directive 89/336/EEC, 
with amendments 92/31/EEC and 93/68/EEC through conformance 
with the following standards:
•  EN 50082-2 (1993)
EN 55011 (1990) Class A
•  EN 61000-6-2 (1999)
EN 61000-4-3 (1996) 10 V/m
EN 61000-4-6 (1996) 10 V/m (all ports)
EN 61000-4-2 (1995) ±8 kV Air Discharge
±4 kV Contact discharge
EN 61000-4-4 (1995) ±2 kV Power port
±1 kV Other ports
EN 61000-4-5 (1995) ±0.5 kV Power ports (DM/CM)
±1 kV Signal ports
EMC Compliance (CE)Additional installation and operating 
instructions
Attention!
•  ATTENTION – RISQUE D’EXPLOSION – LE REM-
PLACEMENT DE TOUT COMPOSANTS INVALIDE LA 
CERTIFICATION CLASS I, DIVISION 2.
•  ATTENTION – RISQUE D’EXPLOSION – EN ZONE 
EXPLOSIVE, VEUILLEZ COUPER L’ALIMENTATION 
ÉLECTRIQUE AVANT LE REMPLACEMENT OU LE 
RACCORDEMENT DES MODULES.
•  ATTENTION – RISQUE D’EXPLOSION – NE PAS 
DÉCONNECTER L’ÉQUIPEMENT TANT QUE 
L’ALIMENTATION EST TOUJOURS PRÉSENTE OU 
QUE LE PRODUIT EST TOUJOURS EN ZONE EXPLO-
SIVE ACTIVE.