Instructions
About the Anybus Communicator for PROFIBUS 9
Doc: HMSI-27-306, Rev. 3.11Anybus Communicator PROFIBUS User Manual
1.2 Status LEDs
1.3 Configuration Switches
The configuration switches are used to set the PROFIBUS node address. Normally, 
these switches are covered by a plastic hatch. Note that the node address cannot be 
changed during runtime, i.e. the gateway requires a reset for changes to have effect.
The configuration is done using two rotary switches as follows:
Node Address = (Switch B x 10) + (Switch A x 1)
Note: When removing the hatch, avoid touching the circuit boards and components. 
If tools are used when opening the hatch, be cautious.
Example:
If the node address should be 42, set switch A to “2” 
and switch B to “4”.
# State Status
1 - Fieldbus Online Off Not online
Green Online
2 - Fieldbus Offline Off Not offline
Red Offline
3 - (Not used)
- -
4 - Fieldbus Diag Off No diagnostics present
Red, flashing 1Hz Error in configuration
Red, flashing 2Hz Error in user parameter data
Red, flashing 4Hz Error in initialisation
5 - Subnet Status
a
a. This led turns green when all transactions have been active at least once. This 
includes any transactions using “change of state” or “change of state on trigger”. If 
a timeout occurs on a transaction, this led will turn red.
Off Power off
Green, flashing Running correctly, but one or more trans-
action error(s) have occurred
Green Running
Red Transaction error/timeout or subnet 
stopped
6 - Device Status Off Power off
Alternating Red/Green Invalid or missing configuration
Green Initializing
Green, flashing Running
Red
Bootloader mode
b
b. The gateway is in bootloader mode, and firmware must be restored in order for it to 
work properly. Start up the Anybus Configuration Manager and connect to the Any-
bus Communicator. Choose Tools/Options/Module. Click “Factory Restore” to 
restore firmware. See “Tools” on page 21.
Red, flashing If the Device status LED is flashing in a 
sequence starting with one or more red 
flashes, please note the sequence pattern 
and contact the HMS support department
1
3
5
2
4
6
A
B
Switch A
Switch B
2
4