User manual

Advanced Configuration 43 (46)
Meter Configuration File
Parent Element name Description Default value Example
root version Version of XML specification
-
0x08
meter
Parent element for each meter
- -
meter
interface Interface to meter
-
M-Bus
serial Serial number of meter
(hexadecimal notation with leading 0x)
0xFFFFFFFF 0x30101198
manufacturer Manufacturer of meter (abbreviation) Not set SLV
version Version of meter Not set 0x01
medium Medium of meter
(see Meter Data Format, p. 26)
Not set Electricity
primaryaddress Primary address of meter
(M-Bus or S0)
0 0x03
addressmode Used mode for addressing:
0 = Secondary,1 =: Primary
0 0
readoutcycle Specific read-out interval (seconds) 0 900
maxvaluecount Limit for number of meter values 0 12
encryptionkey Encryption key for meter (AES for
wM-Bus)
Not set, 0 0x82 0xB0 0x55 0x11 0x91
0xF5 0x1D 0x66 0xEF 0xCD
0xAB 0x89 0x67 0x45 0x23
0x01
active Enables logging of meter data or
transmission via WAN interface
1 1
rssi Received Signal Strength Indicator at last
reception (wM-Bus)
0 123
register Allocated Modbus register 0 20
value Parent element for meter values
- -
value description Description of value
(see Meter Data Format, p. 26)
None Energy
unit Unit of value
(see Meter Data Format, p. 26)
None Wh
encodetype Coding of value NODATA INT32
scale Scale factor (scientific notation) 1e0 1e-3
valuetype Type of value: instantaneous, maximum,
minimum, errorstate
instantaneous instantaneous
storagenum
Storage number of value 0 2
tariff Tariff information for value 0 3
confdata Generic data, OBIS code for value (X-X:X.
X.X*X; X=0...255)
(OBIS-ID in tab Meter)
Not set 0x01 0x00 0x01 0x08 0x00
0xFF
active Enables logging of value data or
transmission via WAN interface
1 1
register Allocated Modbus register 0 30
user
User specified, max. 50 chars
(User label in tab Meter)
Not set OG-1-Re
M-Bus to Modbus-TCP Gateway User Manual SCM-1202-0096-EN 2.1