User manual
Advanced Configuration 42 (46)
System Configuration File (chip.ini) (continued)
Parameter Description Valid range Default value
MUC_LOG Sets the level for output of system data to STDOUT DEFAULT,NONE,ERRORON-
LY,ALL
DEFAULT
MUC_METERDESCRIPTION_
ENABLEFLAGS
Enable flags that control the display of the descripton field in the meter view:
Bit 0 = Description
Bit 1 = Storage-number, tariff, value type
Bit 2 = DIF/VIF raw data
Bit 3 = Complete raw data of meter value entry
0-16 1
MUC_SETDEVICES Activates writing of meter values S0,ALL,NONE S0
MUC_PROTOCOL_VER Protocol version for CSV and XML data 0, 1, 2, 3 30
MUC_SHOWTIMESTAMPENTRIES Explicit display of the meter timestamp 0, 1 0
MUC_USE_FREEZE Enables using the Freeze command prior to meter read-out 0, 1 0
SNTP_ENABLE Enables obtaining system time via SNTP 0, 1 1
SNTP_MAXTIMEOUT Maximum timeout for time request from a SNTP server (seconds) 1 - 4294967295 93600
SNTP_MINTIMEOUT Minimum timeout for a time request from a SNTP server (seconds) 1 - 4294967295 79200
SNTP_REQTIMEOUT Timeout for the SNTP request (ms) 1 - 65535 30000
SNTPIP IP address of SNTP time server Text (max. 40 characters) ptbtime1.ptb.de
WATCHDOG_IDLE Timeout for watchdog during idle state (seconds) 1 - 4294967295 120
WATCHDOG_PROCESS Timeout for watchdog during busy state (seconds) 1 - 4294967295 900
WATCHDOG_READOUT Timeout for watchdog during read-out (seconds) 1 - 4294967295 4 times the read-out
cycle, at least:
WATCHDOG_
PROCESS
WATCHDOG_SCAN Timeout for watchdog during scan process (seconds) 1 - 4294967295 1800
WEBCOM_TIMEOUT Timeout for a web session, user is logged out automatically after that period (ms) 1 - 4294967295 30000
[FTP]
CERT_COUNTRY
Certificate information for SFTP connection
Text SE
CERT_STATE Text Halland
CERT_LOCATION Text Halmstad
CERT_ORGANISATION Text HMS Industrial
Networks
CERT_ORGANISATION_UNIT Text BU Anybus
CERT_COMMON_NAME Text www.hms-networks.
com
[UDPCFG]
IPCFG_PASSWORD Password for IP configuration Text admin
M-Bus to Modbus-TCP Gateway User Manual SCM-1202-0096-EN 2.1