User manual

Advanced Configuration 41 (46)
System Configuration File (chip.ini) (continued)
Parameter Description Valid range Default value
MBUS_SECMASKMEDIUM Predefined medium ID for secondary scan Exactly 2 characters, 0-9 each
or 0xFFFF
0xFF
MBUS_SECMASKSERIAL Mask for serial number of meters for secondary scan Exactly 8 characters, 0-9 or 0xF
each
0xFFFFFFFF
MBUS_SECMASKVERSION Predefined version number for secondary scan Exactly 2 characters, 0-9 each
or 0xFFFF
0xFF
MBUS_SELECTMASK Disables parts of secondary address for exact selection, wildcards are used instead
(set via bit mask):
+1 = Serial number, +2 = Manufacturer, +4 = Version, +8 = Medium
0 - 15, 0
MBUS_STOPBITS Stop bits for serial M-Bus communication 1, 2 1
MBUS_TIMEOUT Timeout for M-Bus (ms) 0 - 65535 2000
MBUS_WAKEUPENABLE Enables specific wake-up request 0, 1 0
METER_MAXALLVALUECOUNT Limits the total number of meter values (0 = no limit) 0 - 65535 0
METER_MAXDEVICECOUNT Limits the number of meters (0 = no limit) 0 - 65535 0
METER_MAXVALUECOUNT Limits the number of meter values per meter (0 = no limit) 0 - 65535 0
METER_STAT_CONFIG Path for meter configuration file Text (max. 40 characters) /app/Device_Handle.
cfg
METER_TIME Interval for meter read-out (seconds)
IMPORTANT: Short cycle times and/or many meters may cause very high amounts
of data being generated.
10 - 4294967295 900
MODBUS_ADDRESS Modbus primary address or unit identifier 0 - 255 0
MODBUS_CONNECTIONTIMEOUT Connection timeout (seconds) 0 - 65535 60
MODBUS_DEBUGOUT Enables the debug output of Modbus data 0, 1 0
MODBUS_DISCONNECTTIMEOUT Timout for disconnection of an idle connection (seconds) 1 - 1000 60
MODBUS_ENABLE Enables the Modbus slaves 0, 1 0
MODBUS_MAXCONNECTIONS Maximum count of simultaneous Modbus TCP connections 0 - 80 5
MODBUS_NWPORT Network port of the Modbus slave 0 - 65535 502
MODBUS_SWAP Swap byte order of Modbus data
0: MSB first
1: LSB first
0, 1 0
MODBUSMETER_
PROTOCOLVERSION
Protocol version of the Modbus meter data:
Bit 0 = 2 registers per value (float-only)
Bit 1 = Multislave
Bit 2 = Word-Swapping of 32-bit values
Bit 3 = Dummy-mode
0 - 16 0
MUC_CONFIG_VER Version of the configuration file 1, 2 2 (explicit)
M-Bus to Modbus-TCP Gateway User Manual SCM-1202-0096-EN 2.1