Troubleshooting 32 (46)
7.2 Network Errors
Web interface and FTP server inaccessible
1. Run Net discover and check if the gateway appears in the list.
If the gateway is not listed, continue to No network connection.
If the gateway is listed:
Run a connection test (ping).
Try to access the FTP server in the gateway.
No network connection
The gateway cannot be accessed and is not visible in Net discover.
1. Check the physical connection (cables and connectors).
Check that the link LED on the Ethernet port of the gateway shows an amber light and that
the activity LED is flashing green. See also Connections and Indicators, p. 7.
Check the corresponding LEDs on the remote terminal (computer, switch, etc.).
If necessary, replace the cables and try again.
2. If the gateway is still not visible in Net discover, check that communication is not blocked by
a firewall. Contact your network administrator if in doubt.
3. If the gateway is visible in Net discover now, run a connection test (ping).
If no ping reply is received and the gateway is connected via a local network, try using a
direct network connection to the computer instead.
The following example IP configuration can be used with a direct connection:
IP Adress Subnet mask
Computer 192.168.1.100 255.255.0.0
gateway 192.168.1.101 255.255.0.0
Do not connect any other network devices to the computer except the gateway when using a
direct connection. A crossover Ethernet cable may be required.
No write access to the web interface
The web interface is accessible but the settings cannot be changed.
1. Make sure that you are logged in as a user with write access.
2. Write access is only allowed for one of the currently logged in users. If another user with
write access is already logged in, they will have to log out before you can log in with write
access.
If you are the only logged in user that has write access:
Check if you have another active session in a different browser or browser tab. Close all
other sessions except the one you are using.
A previous session may not have been closed properly. Try clearing the web browser
cache (see the documentation for your browser).
3. Log in as admin and edit the access rights for the user.