4.5 Server Tab
This tab provides settings for the Modbus TCP interface.
Fig. 9 Server tab
Server tab fields
Field Description Writable
Modbus mode Select Modbus TCP (default) or Modbus UDP.
A maximum of 5 simultaneous connections from Modbus masters are
accepted in Modbus TCP mode.
Yes
Modbus port Port number that the Modbus TCP client (master) should connect to.
Default = 502.
Yes
Modbus test Activates a dummy process image for testing purposes.
See Modbus TCP Specification, p. 22.
Yes
Modbus swap Swap the byte order from MSB first (default) to LSB first. Yes
Modbus float only Use a compressed register layout with double words per value and only
the floating point representation of a meter value.
Yes
Modbus multi slave Represent each meter as an individual Modbus slave address. Yes