Advanced features 39
Anybus M-Bus to Modbus-TCP Gateway User Manual Doc: HMSI-27-300, Rev: 1.10
MBUS_PARITY M-Bus parity:
0: no,
1: odd,
2: even,
3: mark,
4: space
0-4 2
MBUS_RAWLOGENABLE Enables raw data log to drive B: 0, 1 0
MBUS_REQUESTMODE Defines request sequence for read-out DEFAULT,
EXT,
ONLY,
FREEZE
DEFAULT
MBUS_RESETDISABLE Disables reset command 0, 1 0
MBUS_RESETMODE Reset mode:
0: Reset after select,
1: Reset prior to select
2: No reset
0-2 0
MBUS_SCANMODE Scan mode for M-Bus PRIMARYSCAN,
SECONDARYSCAN,
SECONDARYSCANALLOC,
SECONDARYSCANREVERSE,
SECONDARYSCANALLOCRE-
VERSE
SECONDARYSCAN
MBUS_SECMASK
MANUFACTURER
Predefined manufacturer ID for secondary
scan
Exactly 4 characters, 0-9 each or
0xFFFF
0xFFFF
MBUS_SECMASKMEDIUM Predefined medium ID for secondary scan Exactly 2 characters, 0-9 each or
0xFFFF
0xFF
MBUS_SECMASKSERIAL Mask for serial number of meters for sec-
ondary scan
Exactly 8 characters, 0-9 or 0xF
each
0xFFFFFFFF
MBUS_SECMASKVERSION Predefined version number for secondary
scan
Exactly 2 characters, 0-9 each or
0xFFFF
0xFF
MBUS_SELECTMASK Disables parts of secondary address for
exact selection, wildcards are used instead
(set via bit mask):
+1: Serial number
+2: Manufacturer
+4: Version
+8: Medium
0 - 15, 0
MBUS_STOPBITS Stop bits for serial M-Bus communication 1, 2 1
MBUS_TIMEOUT Timeout for M-Bus (in ms) 0 - 65535 2000
MBUS_WAKEUPENABLE Enables specific wake-up request 0, 1 0
METER_MAXALL
VALUECOUNT
Limits the total number of meter values (0:
no limit)
0 - 65535 0
METER_MAXgateway
COUNT
Limits the number of meters (0: no limit) 0 - 65535 0
METER_MAXVALUE
COUNT
Limits the number of meter values per
meter (0: no limit)
0 - 65535 0
METER_STAT_CONFIG Path for meter configuration file Text, max. 40 characters A:\gateway_handle.cfg
METER_TIME Interval for meter read-out (in s), huge
amount of data may arise on short cycle
times and with many meters
10 - 4294967295 900
MODBUS_DEBUGOUT Enables the debug output of Modbus data. 0, 1 0
MODBUS_ENABLE Enables the Modbus slaves 0, 1 0
MODBUS_NWPORT Network port of the Modbus slave 0 - 65535 502
MUC_CONFIG_VER Version of configuration file 1, 2 2 (explicit)
Parameter Description Valid range Default value