Instructions
Configuration 13
Anybus M-Bus to Modbus-TCP Gateway User Manual Doc: HMSI-27-300, Rev: 1.10
Configuration tab fields
Field Description Write access
Readout interval (s) Standard readout cycle of meters (in seconds). Value might be overwritten for each
meter by parameter Cycle in tab Meter
Yes
Description mode Mode of displaying the meter value description on the website:
None: No display of description
Standard: Display of common value description
Extended: Extended display of value description (parameters will be displayed if they dif-
fer from 0):
Notation:Description [Memory No.] <Tariff> {min|max|error}
Example:Energy [2] <1> {max}
Extended with DIF/VIF: Extended display including DIF and VIF raw data
Notation:Description [Memory No.] <Tariff> {Value Type} # XX XX XX …
Example:Energy [2] <1> # 8C 11 04
Extended with raw data: Extended display including the raw data oft he complete meter
value entry.
Notation corresponds to Extended with DIF/VIF:
Example:Energy [2] <1> # 8C 11 04 96 47 06 00
DIF/VIF:
Display of DIF/VIF raw data
Raw data:
Displays the raw data oft he complete meter value entry
After changing this parameter a readout is needed to update the meter list and to display
the relevant data.
Yes
Maximum gateway count Limitation of the number of meters to scan. (0: no limitation).
Already configured meters are not limitated by this parameter.
Yes
Maximum value count Limitation of the number of meter value entries to read during a readout (0: no limitation).
Already configured meter value entries are not limitated by this parameter.
Yes
RAW log active Activates the raw data log. Yes
M-Bus mode M-Bus scan mode (secondary, reverse secondary or primary search) Yes
Primary start address First address for primary search Yes
Primary final address Last address for primary search Yes
Secondary address mask Search mask for secondary search, 8 numerical characters; „F“ defines a wildcard; miss-
ing characters will be filled up with leading zeros
Yes
M-Bus baud rate Baudrate for M-Bus communication (300-19200 baud) Yes
M-Bus timeout M-Bus timeout until reception of first data (in ms) Yes
M-Bus idle timeout M-Bus timeout until end of reception (in ms) Yes
M-Bus full timeout M-Bus timeout (complete) for reception of a whole data packet (in ms) Yes
M-Bus request mode Mode of the M-Bus readout (REQ_UD2):
Standard: Readout with REQ_UD2
Extended 1: Readout with Get-All-Data (DIF/VIF 7F 7E) and REQ_UD2
Extended 2: Readout with Get-All-Data (DIF 7F) and REQ_UD2
Yes
M-Bus reset mode Mode of the M-Bus Reset (before scan and readout):
None: no reset
Standard: Send SND_NKE to primary address of the meter or broadcast address when
using secondary adressing
Extended 1:
Send SND_NKE to primary address FD and SND_NKE to primary address of the meter
or broadcast address when using secondary addressing
Extended 2: Send SND_NKE and an Application Reset to primary address FD and a
SND_NKE to the primary address of the meter or to broadcast address when using sec-
ondary addressing.
Yes
M-Bus max. multipage Limits the count of multipage requests Yes