Meter tab fields
The arrangement of data in the meter list corresponds to the order of the data in the M-Bus protocol.
The meaning of the values can thus be compared directly with the data sheet of the meter. It is also pos-
sible to assign the meter values to the raw data of the meter (see 3.1.3
Configuration tab).
Timestamps transmitted within the M-Bus protocol are automatically assigned to the other meter values
where possible. Therefore, some of these may not appear in the list.
The configuration parameter MUC_SHOWTIMESTAMPENTRIES offers the possibility to manually
enable the display of all time stamps (see 7.4.1
System configuration file).
If a scan or a change in the meter list is terminated with the error message “Webserver capacity exceed-
ed”, see 6.3.6
Webserver capacity error message.
Meters that are not found during a scan, or that do not support an automated scan, can be added man-
ually to the meter list using the button
Add or the context menu entry Add meter.
See also 5.1.2 Adding meters manually
.
Field Description Write access
Interface Interface of meter (M-Bus) No
S Entry status – E indicates that value has been edited Yes
Serial Serial number of meter No
MAN Manufacturer of meter (abbreviation) No
Medium Medium of meter (see 5.2.1
Predefined Media ID Values)No
Version Version number of meter No
Value Meter reading or measurement value No
Scale Scale factor (scientific notation) No
Unit Unit (see 5.2.1
Predefined Media ID Values)No
Cycle Readout interval in seconds (entering 0 means using the general readout interval) Yes
User label User specific description of meter or value.
Included in export of CSV data, allows application specific mapping.
Yes
Description Description of meter value (see 5.2.1
Predefined Media ID Values)No
Register Modbus register address, in steps of 10 (see 5.2.4
Modbus register layout)Yes
Active Activates the transfer of meter or meter value via Modbus TCP Yes