Anybus M-Bus to Modbus-TCP Gateway User Manual Doc: HMSI-27-300, Rev: 1.10
Chapter 3
3. Configuration
The Anybus M-Bus to Modbus-TCP Gateway is normally configured via the web interface, which gives
access to all gateway parameters, meter configuration and services. The gateway can also be configured
by uploading configuration files directly to the gateway via FTP, see 7.
Advanced features.
3.1 The web interface
Auto login
The first time you access the web interface you will be automatically logged in with the default username
and password. You can also log in as the default user manually by clicking
Default Login on the login
screen. The default user only has read access.
If the default user has been disabled in the configuration, you need to enter a valid username and pass-
word and click
Login. See also 3.1.6 User tab.
Default users and passwords
Changes to the files and file system should only be carried out by trained
personnel as it may restrict the functionality of the gateway.
If you are logged in with write access you should always log out after finishing the
configuration, as only one user with write access can be logged in at a time. If
your session stays active, other users will not be able to log in with write access.
User Password Description
admin admin Administrator user with root access, allows full access to all services
(HTTP, FTP, flash update, IP configuration).
web web Default user for the web interface. Allows write access to the web interface.
If a user with this name and password exists, the web server will automatically log in
with these credentials when accessed.
ftp ftp User for FTP access to the log directory (C:/log/)