Install Instructions

Installation Information
Air Flow Interlocking Switch
Specifications
Electrical
10A @ 125, 8A @ 250, 7A @ 277 VAC
1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC
Pilot Duty 125 VA @ 125/277 VAC
All Models
Maximum surge pressure: 20” W.C.
Maximum ambient temperature: 170°F
Minimum ambient temperature: -40°F
Model- SMD
You are installing one of the finest switches of its type on the
market. You will find this switch has many superior features
that insure dependable, accurate long life operation. This
switch is highly sensitive and fully approved. It is UL and
CSA listed, and has FM approval (optional).
Model - SMD
SMDI 1010802016 Rev. A 11/07
R
L
Please read this instruction sheet carefully to
assure correct installation. This equipment must
be installed only by a licensed electrician who is
experienced with combustion safeguard control
systems and understands the functions of an
interlocking switch such as gas pressure switches.
Prior to being put into operation in conjunction with
the combustion safeguard systems, all switches
should be tested for proper range setting and
proper wiring. Check piping connections and switch
housing for leaks with a soap bubble test. All
exhaust fans and blowers should be inspected and
checked for proper rotation prior to starting up.
R
L
R
L
R
L