Use and installation manual
If the problem or fault noticed is not amongst thoselisted in the table,
consult the "Key to Alarms" tableprovided below.
The information provided below s intended to identifythe alarm signals
which appear on the display (A).
Important
Press button (D) to reset the alarm.
TABLE OF ALARM INDICATIONS
Alarm/Event Cause Remedy
A01 - High temperature
alarm
(in conservation)
Room Temp above set value
If the temperature is not within the
specified range, apply to a qualified
technician
A02 - Low temperature
alarm
(in conservation)
Room Temp below set value
If the temperature is not within the
specified range, apply to a qualified
technician
A03 - Limit temperature
alarm
(in chilling/freezing)
Cell or core temperature higher than
the set value
If the temperature is not within the
specified range, apply to a qualified
technician
A04 - Room probe alarm
Room Probe interrupted Qualified technician required
A05 - Evaporator probe
alarm
Evap Probe interrupted Qualified technician required
A06 - Condenser probe
alarm
Cond Probe interrupted Qualified technician required
A07 - Dirty condenser
alarm
Condenser dirty Clean the condenser
A08 - Point needle probe
alarm
Needle Probe interrupted Qualified technician required
A09 - Underskin needle
probe alarm
Sub-dermis needle probe interrupted Qualified technician required
A10 - External needle
probe alarm
External needle probe interrupted Qualified technician required
A11 - Electr.box probe
alarm
Electrical panel probe interrupted Qualified technician required
A12 - Electr.box over-
temp. alarm
Electrical panel temperature higher
than the set value
Qualified technician required
A13 - Open door alarm
QC room door open
Door micro faulty
Close the door
Qualified technician required
A14 - BlackOut alarm
No power supply
When power is restored, check the
max. temperature reached inside the
room
A15 - High pressure
alarm
Intervention by high pressure switch Qualified technician required
A16 - Low pressure
alarm
Intervention by low pressure switch Qualified technician required
A17 - Compressor over-
load alarm
Compressor thermal relay on Qualified technician required
A