User's Manual

4. Commissioning
MF0123A1F_FCC_uc Manual for PSR 700/800 MHz
Page 31
Pinning of M12 Circular Plug-12P (male)
Detail view A
Relay
Pin
Name
Color
1
1
NC
brown
2
NO
blue
3
CC
white
2
4
NC
green
5
NO
pink
6
CC
yellow
3
7
NC
black
8
NO
gray
9
CC
red
4
10
NC
violet
11
NO
orange
12
CC
light green
Dry Contacts PSR alarm Information
Dry Contacts
Relay 1
Relay 2
Relay 3
Relay 4
PSR alarm
monitoring
Relay
picture
PSR Alarm
Information
Pins
1,2,3
Pins
4,5,6
Pins
7,8,9
Pins
10,11,12
Donor Antenna
Disconnection
NO+CC
NC+CC
NC+CC
NC+CC
Donor Antenna
Connection
DL Shutdown
Alarm
NC+CC
NO+CC
NC+CC
NC+CC
System Failure
(failure of critical
system
components)
UL Shutdown
Alarm
NC+CC
NO+CC
NC+CC
NC+CC
PLL Lock Detector
Alarm
NC+CC
NO+CC
NC+CC
NC+CC
Isolation Alarm
NC+CC
NO+CC
NC+CC
NC+CC
Oscillation Alarm
NC+CC
NO+CC
NC+CC
NC+CC
Temperature Alarm
NC+CC
NO+CC
NC+CC
NC+CC
Service Antenna
VSWR Alarm
NC+CC
NC+CC
NO+CC
NC+CC
Antenna Failure
(malfunction of
the donor/ser-
vice antennas)
Donor Antenna
Malfunction
NC+CC
NC+CC
NO+CC
NC+CC
DL HPA Fail Alarm
NC+CC
NC+CC
NC+CC
NO+CC
PA Failure
(failure of active
RF-emitting
devices
UL HPA Fail Alarm
NC+CC
NC+CC
NC+CC
NO+CC
Manual Amp Off
NC+CC
NC+CC
NC+CC
NO+CC
Alarm Status. Normal (NC+CC), Alarm (NO+CC)
Relay Contact: NC 1,4,7,10 / NO 2,5,8,11 / CC 3,6,9,12
4.2.9. LAN Connection
For local access to the PSR user interface via LAN (supplementary use; not mandatory
for operation), connect an RJ485 network cable to the NMS/GUI connector (location see
figure 4-1). Make sure that your local PC meets the requirements specified in chapter
5.1 LAN Settings at Local PC”. This connector is power limited as defined by UL 2524
Chapter 44.1.2 and therefore there is no need to run the connected cable through
conduit.
Note: The length of the connected cable must not exceed 30 meters (98.5 ft).
11