User's Manual
4. Commissioning
MF0123A1F_FCC_uc Manual for PSR 700/800 MHz
Page 29
4.2.8. PSR Alarms Connection
For the location of the ALARM RELAY connector, refer to chapter 4.2.3. The
corresponding cable is part of the delivery:
figure 4-3 PSR alarms cable
Note: The correct connection of this cable to the dedicated annunciator at the site,
which must be part of the building’s fire alarm system, is the sole
responsibility of the installer.
Note: The connected dedicated annunciator must be capable of detecting a single
ground or open. End-of-line resistors with a value of 2.2 k Ohm are installed
between the normally open and common relay contacts to support the
supervision.
Note: The source connected to the ALARM RELAY connector (i.e. the dedicated
annunciator) must be power limited as defined by UL 2524 Chapter 44.1.2
Note: The length of the connected cable must not exceed 30 meters (98.5 ft).
Technical parameters for the delivered alarms cable
Coupling: Thread locking
Environmental characteristics: Ambient temperature: -40°C ~ +90°C
IP rating: IP67
Material:
Technical parameters for the alarm relays
Rated current/voltage: 1A / 24VDC
Contact resistance: <=100m Ohm max.
Insulation resistance: 1000M Ohm min. (500VDC)