Page 42 © April 2019 CommScope, Inc.
Installing a CAP H
Connect the MAINS Power and Power on an AC CAP H
This section provides information for powering an AC CAP H. If you are installing a DC CAP H, go to
"Connect the MAINS Power and Power on a DC CAP H" on page 44.
A MAINS Power cable for AC ships with ea
ch CAP H; see Figure 7. Note that there are two MAINS Power
cables, make sure you are referring to the specifications for the cable with which you are working.
Wiring 1 Wiring 2
Pin Name Color Pin Name Color
1 Phase Black 1 Phase Brown
2 Neutral White 2 Neutral Blue
3 Not connected N/A 3 Not connected N/A
PE Ground Green PE Ground Green/Yellow
Pin PE
Pin 3
Pin 2
Pin 1
MAINS Power Cable PN 7633459-00 ships with
CAP H 8/9/18/21 and CAP H 9/18/21/26
3x1.5mm
2
3.2 m
10.5’
Protecve
cap
Outer diameter of cable is 8.9mm
MAINS Power Cable PN 7633458-01 ships with
CAP H 7E/80 85/17E/19 and CAP H 17E/17E/19/19
3x16AWG
3.2 m
10.5’
Protecve
cap
Outer diameter of cable is 9.9mm
Figure 7. MAINS Power Cable
For the AC power supply connection, a minimum cross section of 1.5 mm2 is required. Each wire must
observe the applicable national regulations regarding loop impedance, voltage drop, and methods of
installation. Make sure to connect the correct voltage to the CAP H
.
MAINS power must be interruptible with an external delay-actions mains breaker. For the MAINS breaker,
observe the following recommendation:
120 Volt / 20 Amp max. or 240 Volt / 16 Amp, single-phase, 50 / 60 Hz AC service is needed, i.e.
the external AC breaker should be 20 Amps max. for 120-Volt service or 13 - 16 Amps for 240-Volt
service.
Do not connect or disconnect the power cord at the mains connector while power is on. Turn off mains
power before connecting the power cord at the CAP H, then, engage mains again.