The TRSN subrack is also available in passive version TRSNx-3, which can be
feeded by direct current (–72 to –36 Vdc). In this case, the -48 Vdc current is
conveyed to the remote units thanks to a passive distribution system (please
refer to fig. 5.45b).
Please read carefully the cabling instructions in order to connect the provided
power cable to the poles of the -48 Vdc connector properly (see fig.5.44b).
Ground terminals are part of the power supply connectors. External grounding
terminals (screw) are also available (see fig. 5.43a,b)
Mains connectors also house the following fuses:
• 250V, 4A delayed type for the active version (feeded by 115 Vac mains
or by 230 Vac mains)
• -48V, 15A delayed type for the passive version (feeded by -48 Vdc
supply)
TRS
TRSN
Fig. 5.44. (a): Power supply connector, fuse, voltage selector and ground screw on the the rear
side of the TRSN subrack feeded by -48 Vdc current TRS/TRSN rear panel. (b) Cabling
instructions for the -48 Vdc connector
(b)
(a)
(
a
)
Fig. 5.45.
(a) Active distribution system used
by a TRS/TRSN subrack feeded by
115Vac-230Vac mains
(b) Passive distribution system used
by a TRSN subrack feeded by a -48
Vdc power supply,