Fan Controller LEDs:
Fan Controller Board
LED Status
Alarm
Severity
Possible Failure Modes
LED 1, 4: GREEN No indication NONE / Disabled
LED 2, 3, 5, 6: GREEN
Normal
Operation
LED 2: RED
Thermistor shorted or open.
LED 3: RED
Fan #3 failed.
LED 5: RED
Fan #1 failed.
LED 6: RED
Fan #2 failed.
Dry Contact Summary Alarms:
ALARM Possible Failure Modes
Door Alarm Intrusion
Fan Alarm
1. Fan controller loses power.
2. Fan is spinning at less than 1900 RPM.
3. Thermistor shorted or open, resulting in no valid thermistor output.
4. Blocked fan rotor.
Rectifier Alarm Rectifier failure
Minor
MPCA Minor Failure: SeeTable 10”, user defined mapping of Door,
Fan, or Rectifier alarms to Minor.
Major
MPCA Major Failure: See “Table 10”, user defined mapping of Door,
Fan, or Rectifier alarms to Major.
Critical
MPCA Critical Failure: SeeTable 10”, user defined mapping of Door,
Fan, or Rectifier alarms to Critical.